Azbil Corporation
Operation using the data setting device
Model MCB10A 5-41
5-6-14 : Setting contact output status
This function is used to set contact output status for normal operation.
This function is effective only when contact output has been selected is the function
specification.
Set range: CLOSE Sets the open collector output to ON.
OPEN
Sets the open collector output to OFF.
Default: OPEN
Set the contact output status in accordance with the following procedure:
Step
Procedure
Screen
1
Enter ENGINEERING MODE in accordance
with the entry into ENGINEERING MODE
(see section 5-4-10). Then press the
h
or
i
key to display the screen at right.
12.3 %
# ST. OUT MODE
NORMAL CLOSE
2
Press the
g
key.
12.3 %
# ST. OUT MODE
NORMAL CLOSE
3
Using the
h
key, set the contact output status.
12.3 %
# ST. OUT MODE
NORMAL OPEN
4
Press the
g
key to move the cursor to the
position under #.
Press the MODE key to return to the
MEASURING MODE and to save data.
12.3 %
# ST. OUT MODE
NORMAL OPEN
CAUTION
You have only ten minutes to return to MEASURING MODE to save the new
value before the system resets it to the previously saved value.