Electrical wiring
Model MCB10A 3-3
Grounding
Grounding should be from the terminal E. Grounding resistance should be less than
100
W
. For the purpose of grounding, make sure to use 3 core cable for power supply
cable.
Grounding resistance should be
less than 100
Ω
.
Figure 3-1 Grounding
Wiring precautions
CAUTION
Incorrect wiring polarity can do damage to the equipment. Reconfirm the wiring
position.
Wire connection of power supply and analog current output
Wire
connection
Terminal
Applicable
conductor
diameter
Applicable
cable
diameter
Recommended
cable
Power supply
+/L
-/N
AWG14-22
6-12 mm
3-core CVV cable
2.0 mm
2
Power
grounding
E
AWG14-22
6-12 mm
3-core CVV cable
2.0 mm
2
Analog output
Iout+
Iout-
AWG16-26
6-12 mm
2-core KEVS cable
AWG16-27
Pulse output
Pout+
Pout-
AWG16-28
6-12 mm
2-core KEVS cable
AWG16-29