Installation
Azbil Corporation
2-56 MagneW
FLEX+/PLUS+
Electromagnetic Flowmeter Detector
Testing continuity
Test the continuity between the following terminals of the trimmed cables.
Table 2-12 Cable continuity
Terminals
Resistance
A - A
0
W
B - B
C - C
Testing the insulation
Test the insulation between the following terminals using an insulation resistance
tester.
Table 2-13 Cable continuity
Terminals
Resistance
A - B
> 100 M
W
,
500 V DC
A - C
B - C
Black
White
A
B
C
65 mm (2.56 inch)
B
A
C
60 mm (2.36 inch)
40 mm (1.57 inch)
70 mm (2.76 inch)
60 mm (2.56 inch)
Black
A
White
B
C
A
B
C
MGG type detector
KID type detector
Figure 2-54 Terminal connections
2.8 : Troubleshooting and maintenance
MagneW
FLEX+/PLUS+
detector is maintenance free.
For device loop diagrams for troubleshooting, operation, and maintenance, refer to
the MagneW
FLEX+/PLUS+
Electromagnetic Flowmeter Model MGG10C/14C User's
Manual (CM2-MGG310-2001).