19
Chapter 3. Operating This Device
Communication setting mode
Transition to
communication
setting mode
Communication setting
(1)
(2)
(3)
(2)
(1) Press and hold the DISP switch for approximately 5 s or more
during the stop status (when the start switch is OFF). The
7-segment display changes to C 1 and the system goes into
communication setting mode. The central dot of the 7-segment
display starts blinking. (a 1 s cycle)
(2) When the DISP switch is pressed, the display changes in the
following order:
→
H
1
→
H2
→
H3
→
CL�
Select a communication setting type using the DISP switch.
Display
Description
H
1
Communication address setting
H2
Baud rate setting
H3
Communications format setting
CL
Initialization of settings
Note
•
For the 200 or 220 V AC model, you can set
H
1
,
H2
, and
H3
even if the power is 100 V AC.
z
Selection of communication setting mode
z
When a selection from
H
1
to
CL
is made
•
Communication address setting (
H
1
)
Use the DISP switch to select
H
1
on the 7-segment display.
1. Press the RESET switch. The 7-segment display shows
H
1
/_. _ is the address value. (Default setting: 1)
2. When the DISP switch is pressed in this situation, the display
cycles through
→
H
1
/
1
→
H
1
/
2
→
H
1
/
3
……
H
1
/
32
.
Select the address.
3. After making a selection, press the RESET switch.
“
H
1
” blinks, and when the blinking ends, configuration is
complete.
At this time,
H
1
is displayed.
•
Baud rate setting (
H2
)
Use the DISP switch to select
H2
on the 7-segment display.
1. Press the RESET switch. The 7-segment display shows
H2
/_. _ represents 1, 2, or 3. (Default setting: 3)
1 : 4800 bps
2 : 9600 bps
3 : 19200 bps
2. When the DISP switch is pressed in this situation, the display
cycles through
→
H2
/
1
→
H2
/
2
→
H2
/
3
.
Select the baud rate.