All cables have a length of about 40 cm.
NOTE: Extension of the power cables must not exceed the following lengths:
6 mm
2
cable cross section:
5 m
10 mm
2
cable cross section: 8 m
The Energypack has one socket which contains (+) and (-) as power contacts and two RJ45 sockets which
contain CAN bus and status and signal lines:
1 socket with power contacts (+) and (-)
1 RJ45 sockets with CAN bus connection for monitoring and control of the
Energypacks by the higher-level controller (X1)
1 RJ45 socket for connecting a further Energypack (X2)
2 M5 threads for connecting the grounding
2.3.5
Ambient conditions
Operation exclusively inside buildings (air-conditioned and non air-conditioned interiors):
Temperature:
0 … 5
0 °C
Relative humidity:
5 ... 85 %
Height:
0 ... 2000 m above sea level.
Temperature Storage: -
20 … 60 °C
2.4 Status und SOC Anzeige
During operation 6 LED fields indicate the status and SOC of the battery system.
Status LED
10 Sekunden
Erklärung
green
–
lights up
unloading
green - flashing
(0,5 s on and 1 s off)
ready (Batterie relay energized
–
waiting for charging or
discharging)
green
–
flashing slowly
(1s on 5 s off)
Standby (battery system relay open)
blue
–
lights up
loading
blue - flashing
(0,5 s on und 1 s off)
Diagnosis or shutdown of the battery system
blue
–
flashing slowly
(1s on 5 s off)
System start, relay test or software update
red
–
flashing fast
(0,2 s on 0,2 s off)
System error - System has disconnected battery from
inverter
red
–
flashing
(0,5 s on und 1 s off)
Error during start-up of the battery system - battery
remains disconnected
Table 4:
Overview LED status codes