Terminals
1, 2
Alarm trigger
Controlled by connection or voltage (10-30 V DC).
Delay 0-5 sec.
Activates siren, 1 sec. - 60 min. and flash.
Volume, 65-90 dB. 0, deactivates sound signal.
3, 4
Reset
Resets the alarm if the door is closed
5, 6
Bypass
Allows the door to be open 1 sec. - 5 min. before the alarm is
activated
DL14 lights up when bypass and relay 1 is activated.
Bypasses the alarm when the door is open and reset the alarm if
the door is closed.
7, 8
Signal
Activates signal, 45-77 dB, and flash. 0, deactivates sound sig-
nal.
Follows the status of the input, no duration control.
9, 10
Supply voltage
10-30 V DC.
9, +
10, GND
Tamper
output
Vandal protection
Indicates both wall removal and opening of housing. Normally
closed.
The contact is closed the shell is shut
11 - 13
Potential free relay output for alarm by pass
Follows the by pass input. Used for lock or by pass.
14 -16
Potential free relay output for alarm
Activates by trigger input.
Dip switch
1. Alarm trigger
2. Signal
3. Reset
4. By pass
4 (17)
Manual UDR Plus