Use recommended cable.  Do not use any un-shield "Twisted Pair" type cable.

Use the largest wire gauge possible.

Use dedicated and linearly regulated power supply, where applicable.

Use Single Point Grounding (Earthing).  No ground loops.

3.3 METAL MOUNTING

The Reader is pre-compensated for mounting on metal utility boxes.

3.4 GENERAL WIRING REQUIREMENTS

All the Reader wiring must be continuously shielded.  AWID recommends using #22

AWG up to #18 AWG, six or seven-conductor shielded cables.  Longer distances and higher

current consumption on the power supply line will require larger gauge wires. Refer to Table 1,

Figure 1 and Figure 2 on the following pages to determine your data lines’ wiring requirement.

Due to system data termination differences, contact your panel manufacturer for their specific

requirements.

WIRE SIZE

#22 AWG (0.6mm Dia)

#18 AWG (1.2mm Dia)

WEIGAND

500ft (152 meters)

980 ft (300 meters)

RS-232

50 ft (15 meters)

50 ft (15 meters)

3.5 POWER SUPPLY

AVOID

using a single power supply for Reader and the magnetic lock. Doing so will affect the

Reader operation and can damage the Reader.

3.6 GROUNDING

Grounding is critical for proper operation of the Reader.  When installing the Reader, it is crucial

to assure that the earth ground is the best ground available.  If you elect to use the AC main

power ground, conduct a test by measuring its resistance relative to a known good ground, such

as a cold water pipe or a structural steel that is in direct contact with the ground. This resistance

should be less than 50 ohms.  If you find that the AC main power does not provide adequate

earth ground, try using a solid

connection to a cold water pipe or for best results drive your own copper clad ground rod into the

earth for the ground point.

For multiple Reader installations, it is critical that all Readers are connected to a single ground

point.  Using multiple ground points will create secondary current paths or ground loops that can

affect the performance and cause damage to the Reader.

3.7 WIRING DIAGRAMS

The Reader is designed for Wiegand and RS-232 standard communication formats; use Figure

1 for Wiegand format installation and Figure 2 for RS-232 format installation. If an external

power supply is being used, leave the Panel’s Ground and Power terminals open and connect

the Reader’s Ground (Black) and 5-12VDC (Red) terminals to the external power supply.

XJ-1023

- 8 -

10/2/2019

Use recommended cable.  Do not use any un-shield "Twisted Pair" type cable.

Use the largest wire gauge possible.

Use dedicated and linearly regulated power supply, where applicable.

Use Single Point Grounding (Earthing).  No ground loops.

3.3 METAL MOUNTING

The Reader is pre-compensated for mounting on metal utility boxes.

3.4 GENERAL WIRING REQUIREMENTS

All the Reader wiring must be continuously shielded.  AWID recommends using #22

AWG up to #18 AWG, six or seven-conductor shielded cables.  Longer distances and higher

current consumption on the power supply line will require larger gauge wires. Refer to Table 1,

Figure 1 and Figure 2 on the following pages to determine your data lines’ wiring requirement.

Due to system data termination differences, contact your panel manufacturer for their specific

requirements.

WIRE SIZE

#22 AWG (0.6mm Dia)

#18 AWG (1.2mm Dia)

WEIGAND

500ft (152 meters)

980 ft (300 meters)

RS-232

50 ft (15 meters)

50 ft (15 meters)

3.5 POWER SUPPLY

AVOID

using a single power supply for Reader and the magnetic lock. Doing so will affect the

Reader operation and can damage the Reader.

3.6 GROUNDING

Grounding is critical for proper operation of the Reader.  When installing the Reader, it is crucial

to assure that the earth ground is the best ground available.  If you elect to use the AC main

power ground, conduct a test by measuring its resistance relative to a known good ground, such

as a cold water pipe or a structural steel that is in direct contact with the ground. This resistance

should be less than 50 ohms.  If you find that the AC main power does not provide adequate

earth ground, try using a solid

connection to a cold water pipe or for best results drive your own copper clad ground rod into the

earth for the ground point.

For multiple Reader installations, it is critical that all Readers are connected to a single ground

point.  Using multiple ground points will create secondary current paths or ground loops that can

affect the performance and cause damage to the Reader.

3.7 WIRING DIAGRAMS

The Reader is designed for Wiegand and RS-232 standard communication formats; use Figure

1 for Wiegand format installation and Figure 2 for RS-232 format installation. If an external

power supply is being used, leave the Panel’s Ground and Power terminals open and connect

the Reader’s Ground (Black) and 5-12VDC (Red) terminals to the external power supply.

XJ-1023

- 8 -

10/2/2019

Use recommended cable.  Do not use any un-shield "Twisted Pair" type cable.

Use the largest wire gauge possible.

Use dedicated and linearly regulated power supply, where applicable.

Use Single Point Grounding (Earthing).  No ground loops.

3.3 METAL MOUNTING

The Reader is pre-compensated for mounting on metal utility boxes.

3.4 GENERAL WIRING REQUIREMENTS

All the Reader wiring must be continuously shielded.  AWID recommends using #22

AWG up to #18 AWG, six or seven-conductor shielded cables.  Longer distances and higher

current consumption on the power supply line will require larger gauge wires. Refer to Table 1,

Figure 1 and Figure 2 on the following pages to determine your data lines’ wiring requirement.

Due to system data termination differences, contact your panel manufacturer for their specific

requirements.

WIRE SIZE

#22 AWG (0.6mm Dia)

#18 AWG (1.2mm Dia)

WEIGAND

500ft (152 meters)

980 ft (300 meters)

RS-232

50 ft (15 meters)

50 ft (15 meters)

3.5 POWER SUPPLY

AVOID

using a single power supply for Reader and the magnetic lock. Doing so will affect the

Reader operation and can damage the Reader.

3.6 GROUNDING

Grounding is critical for proper operation of the Reader.  When installing the Reader, it is crucial

to assure that the earth ground is the best ground available.  If you elect to use the AC main

power ground, conduct a test by measuring its resistance relative to a known good ground, such

as a cold water pipe or a structural steel that is in direct contact with the ground. This resistance

should be less than 50 ohms.  If you find that the AC main power does not provide adequate

earth ground, try using a solid

connection to a cold water pipe or for best results drive your own copper clad ground rod into the

earth for the ground point.

For multiple Reader installations, it is critical that all Readers are connected to a single ground

point.  Using multiple ground points will create secondary current paths or ground loops that can

affect the performance and cause damage to the Reader.

3.7 WIRING DIAGRAMS

The Reader is designed for Wiegand and RS-232 standard communication formats; use Figure

1 for Wiegand format installation and Figure 2 for RS-232 format installation. If an external

power supply is being used, leave the Panel’s Ground and Power terminals open and connect

the Reader’s Ground (Black) and 5-12VDC (Red) terminals to the external power supply.

Summary of Contents for uAxcess XJ-1023

Page 1: ...uAxcess XJ 1023 Users Manual 041419 uAxcess XJ 1023 Users Manual 041419 uAxcess XJ 1023 Users Manual 041419...

Page 2: ...rence received including interference that may cause undesired operation NOTE This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to part 15 of the...

Page 3: ...Note The country code selection is for non US model only and is not available to all US model Per FCC regulation all WiFi products marketed in US must be fixed to US operation channels only...

Page 4: ...FOR INSTALLATION 7 3 1 Site Survey 7 3 2 Preferred reader installation practices 7 3 3 Metal mounting 8 3 4 General wiring requirements 8 3 5 Power Supply 8 3 6 Grounding 8 3 7 Wiring Diagrams 8 4 WA...

Page 5: ...REVISION HISTORY Version No Revised By Date Sections Affected Remarks 1 0 AWID Engineering 9 2019 Initial version 1 1 AWID Engineering 10 2019 FCC ID assigned OGS1356RM...

Page 6: ...dance applications 1 1 GENERAL DESCRIPTION Thin line switch plate mounting LED visual indicator Indoor installation Audible feedback 1 2 SPECIAL FEATURES Simultaneous Wiegand Access Control and RS 232...

Page 7: ...before starting installation avoid any possible sources of interference If the Reader is not installed properly the performance will be degraded or more seriously the Reader may be damaged The followi...

Page 8: ...mage the Reader 3 6 GROUNDING Grounding is critical for proper operation of the Reader When installing the Reader it is crucial to assure that the earth ground is the best ground available If you elec...

Page 9: ...urchaser to be free of defects in material and workmanship for the life of the product Any tampering or modification to the product will void this product warranty AWID does not warrant any product as...

Reviews: