INSTRUKCJA MONTAŻU

OGÓLNE WARUNKI GWARANCJI dostępne są na stronie internetowej producenta www.awex.eu

Zamówiony towar wyprodukowany wg indywidualnego zamówienia odbiegający od standardowej oferty firmy Awex nie podlega zwrotowi.

SPECYFIKACJA TECHNICZNA:

- Napięcie zasilania: 220 - 240VAC/50 - 60Hz, 176 - 275VDC, 24VDC
- Klasa izolacji: II lub III
- Stopień ochrony: IP44
- Czas pracy w trybie awaryjnym: 1, 2 lub 3h
- Źródło światła:1W, 2W lub 3x1W LED
- Czas ładowania akumulatora: maksymalnie do 24h
- Temperatura otoczenia: 0 - +40°C
- Odległość rozpoznawania: 25m

CECHY CHARAKTERYSTYCZNE:

- Sygnalizacja ładowania akumulatora za pomocą diody LED
- Elektroniczne zabezpieczenie przed rozładowaniem baterii
- Funkcja automatycznego testowania (opcjonalnie)
- Możliwość pracy w trybie awaryjnym lub sieciowo - awaryjnym
- Możliwość zastosowania do systemu monitorowania Rubic
- Możliwość zastosowania do centralnej baterii
- Montaż podtynkowy do sufitu 
- Korpus oprawy wykonany z poliwęglanu, szyba z plexi
- Oprawa może być zasilana ciągle lub nieciągle
- Montaż do powierzchni płaskich wewnątrz budynku
- Oprawa jest wyposażona w moduł, który pozwala zmieniać 
  tryb pracy na awaryjny

ZALECENIA UŻYTKOWE:

Aby zapewnić prawidłową i bezawaryjną prace oprawy należy przestrzegać 
następujących zasad:
- Pakiety akumulatorów muszą współpracować z modułami awaryjnymi
- Instalację oprawy powinna wykonywać odpowiednia osoba, do takich 
  czynności uprawniona
- Po zainstalowaniu oprawy powinno nastąpić formatowanie akumulatora 
  poprzez ciągle ładowanie w okresie 24h i pełne rozładowanie świeceniem
- Należy przeprowadzić trzy pełne cykle formatowania aby uzyskać jak 
  największą pojemność akumulatora
- Raz w roku nalezy przeprowadzić przegląd techniczny oprawy a zwłaszcza 
  akumulatora
- Ważne jest zachowanie parametrów temperaturowych dla pakietów 
  bateryjnych tj. od 0°C do +55°C
- Zabrania sie jakichkolwiek zmian w konstrukcji układu. elektronicznego
- W przypadku gdy oprawa nie zapewnia podtrzymania zasilania dla 
  znamionowego czasu pracy, nalezy wymienić akumulator
- Producent zaleca wymianę akumulatora co 4 lata
- Oprawa jest wyposażona w wymienialne źródło światła
- Znamionowy strumień światła w trybie awaryjnym wynosi 100%.

WARUNKI GWARANCJI:

Warunkiem uznania gwarancji jest:
- Brak uszkodzeń mechanicznych
- Brak śladów ingerencji osób trzecich w konstrukcję oprawy a zwłaszcza 
  modułu awaryjnego
- Prawidłowa eksploatacja zgodna z zaleceniami 
- Prawidłowe podłączenie napięcia zasilającego i pakietu akumulatorowego 
  (UWAGA!, nalezy zwrócić uwagę na biegunowość zacisków baterii i 
  przetwornicy).

TESTOWANIE OPRAWY:

Istnieje możliwość testowania oprawy za pomocą przycisku testu 
umieszczonego w obudowie (opcjonalnie). W momencie podłączenia 
oprawy do napięcia zasilającego zapala się zielona dioda sygnalizująca 
pojawienie się napięcia w układzie elektronicznym a tym samym ładowanie 
akumulatora. Wciśniecie przycisku powoduje aktywacje testu oprawy poprzez 
przerwę w obwodzie a tym samym symulację zaniku napięcia sieciowego i 
przełączenie przez układ elektroniczny w tryb pracy awaryjnej. Podczas pracy 
awaryjnej dioda LED przestaje świecić, oprawa jest zasilana z akumulatora. Po 
zwolnieniu przycisku powraca napięcie sieciowe rozpoczyna się proces 
ładowania.

FUNKCJA AUTOTEST:

Test A wyzwalany jest automatycznie co 28 dni. Podczas wykonywania 
testu A sprawdzane są następujące parametry: wymuszenie pracy awaryjnej oprawy 
na czas 1 min. Kontrola prądu rozładowania akumulatora.
Test B wyzwalany jest automatycznie co 364 dni.Podczas wykonywania 
testu B sprawdzane są następujące parametry: wymuszenie pracy awaryjnej oprawy 
na czas zdeklarowany dla danej oprawy, kontrola prądu rozładowania akumulatora,
kontrola napięcie akumulatora.

TECHNICAL SPECIFICATION

- Supply voltage: 220 - 240VAC/50 - 60Hz, 176 - 275VDC, 24VDC

Insulation class

: II or III

Protection level

: IP44

Time of operation in emergency mode 

: 1, 2 or 3h

Light source

:1W, 2W or 3x1W LED

Battery charging time 

: up to 24h

Ambient temperature 

: 0 - +40°C

- Viewing distance: 25m

MAIN FEATURES

:

Battery charging indication by LED

Electronic protection against total battery discharge

Self-test function (optional)

Operation in emergency or mains and emergency mode available

Using to 

Rubic system

 available

 

Using to central battery available

- Recessed (ceiling) assembly
- Assembly indoors to flat surface  
- Polycarbonate body, plexi glass
- The luminaire can be powered maintained or non maintained
- Controlgear supplied within this luminaire performs the function of 
  changeover operation from normal to emergency mode

RECOMMENDATIONS FOR USE

:

The following rules must be observed to ensure the correct and reliable 
operation of the fitting:

Battery packs must be compatible with emergency modules

Installation of fitting should be made by appropriate person which is 

  

authorized for such works

After installation of fitting, the formatting of battery must be made while 

  

continuous charging for a period of 24 hours and fully discharging it 

  

through lighting

Three full formatting cycles must be performed to achieve maximum 

 

  

battery capacity

Technical inspection of the fitting and, in particular, of the battery must 

  

be performed once a year

It is important to maintain temperature parameters for battery packs, i.e.

 

  

from 0°C to + 55°C

It is forbidden to make any changes in electronic system design

If the fitting does not withstand its rated operation time, the battery must 

  

be renewed

It is recommended by the manufacturer to renew the battery every 4 

years

The fitting is equipped with a replaceable light source

-

 

 Rated luminous flux in emergency mode amounts to 100%

.

TERMS AND CONDITIONS OF WARRANTY

:

The condition to acknowledge the warranty is

:

No mechanical damage

No evidence of changes made by third party in fitting design and, in 

 

  

particular, emergency module

Proper use, as recommended

Proper connection of supply voltage and battery pack (attention must be 

  

paid to the polarity of the battery and converter terminals).

TESTING THE FITTING

:

It is possible to test the fitting using test button placed in the

 

housing (option).

At the time when the supply voltage is connected to the

 

fitting, the green LED lights up indicating the emergence of voltage in the
electronic system and thus the battery charging. By pressing the button, 
the test of fitting is activated through an open circuit, and by this the 
decay of mains voltage is simulated and the switching over by electronic 
system to the emergency operation mode is caused. During emergency 
operation, the LED is no longer lit, the fitting is powered from the battery. 
When the button is released, the mains voltage returns and the fitting is 
operated in mains mode, charging process is started.

AUTOTEST FUNCTION:

Test A is run automatically every 28 days. During test A a conversion kit 
is switched to emergency mode for 1 minute and the following 
parameters are checked: control of battery power discharge,  control of battery.
Test B is run automatically every 364 days. During test B a conversion kit 
is switched to emergency mode for all duration time and the following 
parameters are checked: control of battery power discharge, control of 
minimum battery voltage .

ASSEMBLY INSTRUCTIONS

GENERAL CONDITIONS OF WARRANTY are available on manufacturer's website at www.awex.eu

 

The goods ordered that were manufactured according to the individual order and differ from the standard offer of Awex may be not returned.

LED

24V

DC

Ni-Cd

Ni-MH

IP44

176-275V

DC

220-240V

AC

50-60Hz

d=25m

1

OPRAWA ARROW P 

ARROW P FITTING 

2

WYMIARY OPRAWY ARROW P

ARROW P

 FITTING

 

3

DEMONTAŻ OPRAWY ARROW P

DISASSEMBLING ARROW P

 FITTING

 

A

B

ARROW P

LP. 

Źródło światła

Opis

1

dowolny

Potwierdzenie resetu czasu lub 

błędów (tylko AT)

2

świeci

Praca awaryjna

3

nie świeci

Tryb spoczynkowy

4

dowolny

Błąd komunikacji (tylko  RS)

5

dowolny

Błąd akumulatora

6

dowolny

Błąd źródła światła lub elektroniki

7

świeci

Wykonywany test lub praca 

sieciowa

8

dowolny

Brak akumulatora 

9

nie świeci

Ładowanie akumulatora  

10

nie świeci

Tryb gotowości (akumulator pełny)

11

nie świeci

Ustawiono za dużą moc wyjściową 

w stosunku do pojemności 

akumulatora

Czerwona dioda
Zielona dioda

Kolor świecenia LED

sygnalizacja błędów albo nie świeci

sygnalizacja błędów albo nie świeci

LP

Light 

source

Description

1

any

Confirmation of the reset of 

timer or errors (AT)

2

shining

Emergency mode

3

not shining

Standby mode

4

any

Communication error (only RS)

5

any

Battery error

6

any

Light source or electronics 

error

7

shining

Performing test or mains mode

8

any

No battery

9

not shining

Battery loading

10

not shining

Standby mode (battery full)

11

not shining

Too much output power for this 

battery capacity

Color of LED indicator shining

Error indication or not shining

Error indication or not shining

Red indicator

Green indicator

202 mm

206 mm

299 mm

230mm

20 mm

132mm

109mm

Ø19

Ø12

Ø43

130mm

206mm

43mm

327mm

130mm

Reviews: