Configure Your Analog Sensor

Reference/Scale/Unit Settings For AVTECH Analog Sensors

AVTECH’s Current Loops

Current Loop 1

Current Loop 2

High

Low

High

Low

Reference

5

0

Reference

5

0

Scale

Scale

With the jumper on

With the jumper on

High (0 to 50 A)

50

0

High (0 to 250 A)

250

0

Middle (0 to 20 A)

20

0

Middle (0 to 200 A)

200

0

Low (0 to 10 A)

10

0

Low (0 to 100 A)

100

0

Units

A (or Amp)

Units

A (or Amp)

AVTECH’s Standard Extreme Temperature Sensors

The values below apply to our standard Extreme Temperature Sensors. If you ordered 

a customized version, please use your custom 

Reference

 and 

Scale

 instead of these 

values.

Standard Extreme Low Temperature Sensor

Conversion To Fahrenheit

Conversion To Celsius

High

Low

High

Low

Reference

5

1

Reference

5

1

Scale

32

-328

Scale

0

-200

Units

F

Units

C

Standard Extreme High Temperature Sensor

Conversion To Fahrenheit

Conversion To Celsius

High

Low

High

Low

Reference

5

1

Reference

5

1

Scale

743

-40

Scale

395

-40

Units

F

Units

C

AVTECH’s Analog Rescaling Module (ARM)

High

Low

Reference

5

1

Scale*

See note 

below.

Units*

*Scale and Units depend on the output of the analog sensor you’ve connected to ARM.

AVT-171211-1.2.0

www.serverroomenvironments.co.uk

Summary of Contents for RMA-CL1-SEN

Page 1: ...ce device being monitored for the most accurate readings Current Loop 1 Current Loop 2 High H 0 to 50 A Middle M 0 to 20 A Low L 0 to 10 A H 0 50A M 0 20A L 0 10A 0 5 VDC COM H M L Use Insulated Conductors Only High H 0 to 250 A Middle M 0 to 200 A Low L 0 to 100 A H 0 250A M 0 200A L 0 100A 0 5 VDC COM H M L Use Insulated Conductors Only To change the setting pull the jumper up to detach it from ...

Page 2: ...or the Current Loop to operate correctly 5 Lock the Current Loop closed by pressing the cover down firmly and listening for the click Step 3 Connect your Current Loop to Room Alert Do not connect the analog inputs on AVTECH products to live circuits of over 5 VDC Use only low voltage 2 wire cable to connect analog inputs Your Current Loop comes with one end of the 25 speaker wire already attached ...

Page 3: ... Features Specifications Environment Condition Monitored Electrical current amps Type Of Sensor Analog Power Supply Induced from monitored conductor Sensor Cable Type Low voltage 2 wire speaker cable Included Yes Length 25 Maximum Extendible Length 100 Output Voltage 0 to 5 VDC Input Amperage Range Current Loop 1 RMA CL1 SEN 0 to 50 A Current Loop 2 RMA CL2 SEN 0 to 250 A Accuracy 1 0 2 to 100 FSO...

Page 4: ... Scroll to your external digital sensor s and find the digital sensor you connected your Temperature Analog Sensor to 2 Enable the sensor by selecting Enabled next to the High Low Adjust fields The built in analog sensor will not appear in the Room Alert web interface Device ManageR your RoomAlert com account or SNMP program unless it is enabled 2 Select Temp Analog from the Sensor Type drop down ...

Page 5: ... Sensor Label you may leave the default Analog Sensor X or enter something more descriptive of up to 15 characters You may use the following characters in sensor labels letters numbers spaces hyphens underscores _ and periods In High and Low you may leave the default 0 which means no alarm is configured or enter values for high and low thresholds These values must be within the range you entered i...

Page 6: ...e Temperature Sensors If you ordered a customized version please use your custom Reference and Scale instead of these values Standard Extreme Low Temperature Sensor Conversion To Fahrenheit Conversion To Celsius High Low High Low Reference 5 1 Reference 5 1 Scale 32 328 Scale 0 200 Units F Units C Standard Extreme High Temperature Sensor Conversion To Fahrenheit Conversion To Celsius High Low High...

Reviews: