![Avid Technology MV3000 DELTA Technical Manual Download Page 64](http://html1.mh-extra.com/html/avid-technology/mv3000-delta/mv3000-delta_technical-manual_3031206064.webp)
Specification
T1689 Technical Manual Rev 07
Reactors, Inductors & Transformers
MV3000 Air Cooled DELTA
Page 64
Reactor Order
Number
Current
Rating
(A r.m.s)
Drive (1.1 x Overload)
Drive (1.5 x
Overload)
Nominal
Supply
Voltage (V)
Approx.
Weight
R
reactor
(m
Ω
)
kg
lb
33Z0329/10
670
1 x MVD500
380-525
60
132 0.8
33Z0331/10
1004
2 x MVD500
380-525
120
264 0.3
50Z0019/01
1860
3 x MVD500
380-525
170
374 0.2
50Z0055/04
2295
4 x MVD500
380-525
TBA
0.4
50Z0055/05
2850
5 x MVD500
380-525
310
682 0.3
50Z0050/07
3405
6 x MVD500
380-525
TBA
50Z0038/01
423
1x MVD300
1 x MVD300
690
100
220 1.2
50Z0038/02
846
2 x MVD300
1 x MVD500
2 x MVD300
690
160
352 0.6
50Z0038/03
1270
3 x MVD300
2 x MVD500
3 x MVD300
690
190
419 0.4
50Z0057/01
1660
4 x MVD300
3 x MVD500
4 x MVD300
690
210
462 0.6
50Z0057/02
2075
5 x MVD300
4 x MVD500
5 x MVD300
690
260
572 0.5
50Z0057/03
2485
6 x MVD300
5 x MVD500
6 x MVD300
690
325
715 0.4
Table 2–32. – DC Link Inductors – Weight & Resistance
2.13.4
Losses
Power loss = Idc² x R
reactor
x 1.3 Watts
Where
R
reactor
is in ohms
Idc is in amperes.