Appendix D: MV3000e Drive Selection Charts
MV3000 Air Cooled DELTA
Ratings MV3000e DELTA Drive Selection Tables
Page 185
13.
APPENDIX D: MV3000E DRIVE SELECTION CHARTS
13.1
RATINGS MV3000E DELTA DRIVE SELECTION TABLES
Assumed Efficiency = 0.95
Ambient = 40
°
C
Altitude = 1000 metres
575 V - 690 V DELTA DRIVES
Assumed Cos
Φ
= 0.9
PWM Frequency = 1.25 kHz
Voltage = nominal
150%/110% OVERLOAD
380-525 V a.c. Units: 110% & 150% Overload
Drive Unit
400V
480V
525V
Amps
Motor
Power
(kW)
Losses
(kW)
Amps
Motor
Power
(kW)
Losses
(kW)
Amps
Motor
Power
(kW)
Losses
(kW)
MVD500-4501 (110% O/L)
500
296
3.80
500
355
4.02
500
389
4.13
MVD500-4501 (150% O/L)
367
218
2.44
367
261
2.60
367
285
2.67
Table 13–1. – MVD500-4501 Ratings in 1.1 & 1.5 Overload
575 – 690 V a.c. Units: 110% & 150% Overload
Drive Unit
575V
600V
690V
Amps
Motor
Power
(kW)
Losses
(kW)
Amps
Motor
Power
(kW)
Losses
(kW)
Amps
Motor
Power
(kW)
Losses
(kW)
MVD500-4701 (110% O/L)
500
427
4.31
495
440
4.32
475
485
4.34
MVD500-4701 (150% O/L)
367
313
2.78
367
326
2.83
367
375
3.03
Table 13–2. – MVD500-4701 Ratings in 1.1 & 1.5 Overload
575 – 690 V a.c. Units: 110% Overload
Drive Units
600V
660V
690V
Amps
Motor
Power
(kW)
Losses
(kW)
Amps
Motor
Power
(kW)
Losses
(kW)
Amps
Motor
Power
(kW)
Losses
(kW)
MV3300 (1 DELTA)
367
326
5.03
360
352
5.06
356
364
5.07
MV3600 (2 DELTA)
705
627
9.67
691
676
9.71
684
699
9.73
MV3900 (3 DELTA)
1058
940
14.50
1037
1013
14.57
1026
1049
14.60
MV31200 (4 DELTA)
1410
1253
19.33
1382
1351
19.42
1368
1398
19.47
MV31500 (5 DELTA)
1763
1566
24.16
1728
1689
24.28
1710
1748
24.34
MV31800 (6 DELTA)
2115
1880
29.00
2074
2027
29.13
2052
2097
29.20
Table 13–3. – MVD300 Ratings in 1.1 Overload