Rack-Mounting the Equipment
58
Securing the Outer Slide Rail to the Rack-Mounting Rail
5. Adjust the outer slide rail bracket assembly to the rear mounting rail.
6. Secure the rear outer slide rail bracket assembly to the rear mounting rail as you did for the
front rack-mounting rail.
7. Repeat this procedure to attach the second outer slide rail on the other side of the rack.
Securing the System Director in a Rack
c
You should have someone helping you lift the System Director while you are positioning it
into the slide rails.
To secure the server to the rack enclosure:
1. Lift and position the server so that the inner slide rails (secured to the System Director) are
aligned with the outer slide rails secured to the rack.
2. Push the front of the System Director server flush against the front mounting rail. The holes
in the server front panel align with the holes in the front mounting rail.
3. From the front of the rack enclosure, insert the large Phillips-head screw through the System
Director and front mounting rail.
-
Square hole racks — the middle hole of the outer rail kit is where the screw anchors the
server front panel to the vertical rail. A M6x10 screw in the parts kit is included to
secure the front panel with square hole racks.
-
Round hole racks — the server front panel attaches to the vertical rail of the rack. Use a
truss head screw or hardware that come with your rack to secure the front panel with
round hole racks.