PNC Cabling — Fiber Hardware
Issue 1 May 2002
2-5
555-233-143
EI-to-SNI or EI-to-EI Intracabinet Metallic
Cabling
Metallic cable may be substituted for optical cable for “fiber” connections between
EIs or between an EI and an SNI in the same MCC cabinet. The same I/O plate
connectors are used. The metallic cables should not be used for intercabinet
connections, since doing so would violate system ground integrity. The metallic
cable comes in two lengths.
DS1 CONV Cabling
When fiber-optic cabling is not practical, digital Service 1 (DS1) can be used to
connect EPNs up to 100 miles (161 km) apart. Whereas, fiber-connected EPNs
must be closer than either of these types of fiber from the switch node carrier:
■
25,000 feet (7.62 km) for multimode
■
22 miles (35.4 km) for single-mode
A TN574 or TN1654 DS1 Converter (DS1 CONV) circuit pack serves as the
interface between the network and an EI or SNI on the switch. DS1 cabling on a
carrier consists of a Y-cable that connects a DS1 CONV to an EI or SNI and to the
network. The following cables may be used, depending upon where the DS1
CONV and the EI or SNI are located:
Part No.
Length
Intended use
H600-278,G1
13 inches
(33 cm)
From an EI in slot 1 of a switch node carrier to an
SNI in the same half of the carrier (usually the
adjacent slot)
H600-278,G2
66 inches
(168 cm)
From an EI to an SNI in the same cabinet, but in a
different carrier or different half of a carrier
Connection Location
Length
Comcode
Number
TN574
Comcode
Number
TN1654
On same half carrier
1 foot (30.48 cm)
846448637
847245750
On different half
carriers in same
cabinet
5.5 feet (1.68 m)
846448645
847245768
Between two adjacent
cabinets
1 foot (30.48 cm),
used with two
9823As, and 1 20-foot
(6.1-m) fiber-optic
cable
846448652, and
one 846885259
bracket
847245776 with
one 846885259
bracket
Summary of Contents for S8700 Series
Page 50: ...Maintenance Architecture 555 233 143 1 26 Issue 1 May 2002 ...
Page 74: ...Initialization and Recovery 555 233 143 3 12 Issue 1 May 2002 ...
Page 186: ...Alarms Errors and Troubleshooting 555 233 143 4 112 Issue 1 May 2002 ...
Page 232: ...Additional Maintenance Procedures 555 233 143 5 46 Issue 1 May 2002 ...
Page 635: ...status psa Issue 1 May 2002 7 379 555 233 143 status psa See status tti on page 7 406 ...
Page 722: ...Maintenance Commands 555 233 143 7 466 Issue 1 May 2002 ...