Media Server alarms
S8300 alarms – UPS
Maintenance of the Avaya G350 Media Gateway
323
June 2004
Table 189: Alarm #58
Number
58
Source
UPS
Event ID
20
Alarm Level
Warning
Alarm Text Description
upsAlarmLowBattery
Possible Causes
Remaining battery run-time is less than or equal to specified
threshold
Determining Cause
Alarm condition present indicates the problem occurred.
Resolution
Return AC input power to UPS
Table 190: Alarm #59
Number
59
Source
UPS
Event ID
21
Alarm Level
Warning
Alarm Text Description
upsAlarmUpsOutputOff
Possible Causes
UPS has shutdown output power as requested
Determining Cause
Alarm condition present indicates the problem occurred.
Resolution
Turn-on output power – can be done via SNMP messages
Table 191: Alarm #60
Number
60
Source
UPS
Event ID
22
Alarm Level
Warning
Alarm Text Description
upsAlarmOutputBad
Possible Causes
Output on one of the receptacles is out of tolerance
Determining Cause
Alarm condition present indicates the problem occurred.
Resolution
Requires diagnosing the UPS – may be simpler to just replace it
and diagnose it later