Installing the Avaya™ S8700 Media Server with Avaya™ MCC1 or SCC1 Media Gateway
Connect the Media Gateway to the MDF
May 2003
Install Connector Cables Between Auxiliary
Cabinet (if used) and MDF
Auxiliary equipment that connects to the MDF can be mounted inside the auxiliary cabinet. The
equipment connects to an ED-1E1443-10 (Group 1) intraconnection panel mounted in the
cabinet. This intraconnection panel consists of a 110-type 100-pair wiring block. Auxiliary
equipment is connected to the 110-type wiring block. The wiring block is pre-wired to four
25-pair female connectors mounted on the outside rear of the cabinet.
1
Install “D” rings on the wall between the cable slack manager and the
terminal/connecting blocks mounted on the MDF.
2
Install a self-sticking port label on the rear of each connector on the B25A connector
cable. See
‘‘Self-Stick Label on 25-Pair Cable Connector’’ on page 120
.
3
Labels should be positioned so the cabinet connector retainers do not obscure them.
4
At the rear of the auxiliary cabinet, connect 1 end of the connector cable to the assigned
connector.
5
Route the cable down the rear of the cabinet and through the cable slack manager to the
MDF.
6
At the MDF, connect the other end of the cable to the assigned terminal/connecting block
connector.
7
Store the excess cable in the cable slack manager.
8
Repeat Steps 2 through 6 until all cables are installed.
Self-Stick Label on 25-Pair Cable Connector