Routine Maintenance Procedures
555-233-123
5-50
Issue 4 May 2002
by the network. The user must subscribe to Test Type 108 service and have
the correct far-end test call number administered on the trunk group form for
the call to be allowed.
Troubleshooting Backplane Voltage
Problems
The TN2036 Voltage Range circuit pack is a test tool that allows easy access to
the backplane pins that provide various voltages to control and port slots. Probes
from a voltmeter can be plugged into the access point for the desired voltage and
a ground access point to measure the voltage. This circuit pack itself has
instructions for use printed on the side as well as a listing of the voltage tolerance
range for each voltage on the front panel. The voltages and tolerances are as
follows:
ringing voltage: 75 -> 115 VAC
+12 VDC: 11.4 -> 12.6 VDC
+5 VDC: 4.95 -> 5.35 VDC
-5 VDC: -4.95 -> -5.35 VDC
-48 VDC: -43 -> -53 VDC
neon message waiting voltage: -80 VDC -> -165 VDC
The type of cabinet determines where the circuit is placed to measure the
voltages. For single-carrier cabinets, all voltages 12 VDC and +5 VDC
can be measured from any port slot. However, the neon message waiting voltage
requires that the system have a TN752 or TN755 Power Unit circuit pack. The
Tape Drive slot is used to m12 VDC.
NOTE:
All control circuit packs should be removed from the backplane before this
measurement is made.
The +5 VDC measurement must be made in two separate cabinet locations since
the power unit has two indep5 VDC outputs [+5 VDC and +5(B) VDC].
Each output supplies a different section of the cabinet with power. For the control
cabinet, make one measurement in the processor slot and another in any port
slot. For an EPN control cabinet, make one measurement in any port slot from 1
to 4 and another in any port slot from 5 to 16. For a port cabinet, make 1
measurement in any port slot from 1 to 6 and another in any port slot from 7 to 18.
Summary of Contents for Definity SI
Page 1: ...0DLQWHQDQFH IRU YD D 1 7 6HUYHU 6 Volumes 1 2 and 3 555 233 123 Issue 4 May 2002...
Page 62: ...Maintenance Architecture 555 233 123 1 26 Issue 4 May 2002...
Page 92: ...Management Terminals 555 233 123 3 26 Issue 4 May 2002...
Page 204: ...Routine Maintenance Procedures 555 233 123 5 100 Issue 4 May 2002...
Page 250: ...LED Interpretation 555 233 123 7 10 Issue 4 May 2002...
Page 2804: ...Maintenance Object Repair Procedures 555 233 123 10 2018 Issue 4 May 2002...