Adding New Carriers and EPN Cabinets
555-233-115
6-2
Issue 7 November 2003
Add MCC Port Carriers
A new port carrier can be installed when additional features or equipment exceed
the capacity of the present system. Port carriers are identified as B, C, D, and E
except for a PPN cabinet with the duplication option. The “B” carrier is the second
control carrier. PEC 63155 provides the necessary equipment for adding the
carrier.
Add each new port carrier to a port network in the “B,” “C,” “D,” “E” order of carrier
positions.
Before proceeding with the addition of a port carrier, ensure that at least 3
TN1650B Memory Circuit Packs exist in the system. Refer to the section entitled
‘‘Add Memory, Replace DUPINT Circuit Pack, and Unseat Disk Drive on SPE A’’
on page 2-34
for installation instructions.
Before proceeding with the addition of a port carrier, ensure that the TN1657 Disk
Drive is of Vintage 9 (or higher). Refer to
‘‘Install V9 or Later Disk Drive(s)’’ on
for installation instructions.
Service Interruption
1. Since the addition of port carriers requires a service interruption, notify the
customer in advance as to when the addition will take place.
Verify System Status
1. Before proceeding, examine the system for alarms. Every problem should
be corrected. The system must be alarm-free.
Disable Alarm Origination
1. Type change system-parameters maintenance and press
Enter
.
2. Make a note of the
Alarm Origination Activated
field. If the feature
is enabled, type n in this field to disable Alarm Origination.
You will enable this feature again in 1 of the final processes.
!
WARNING:
If you do not disable Alarm Origination before making changes to the
switch, the switch may generate alarms, resulting in unnecessary
trouble tickets. Reducing redundant and unnecessary trouble tickets
is critical for measuring the quality of Avaya services and products.
NOTE:
For some releases of the software, disable
Cleared Alarm
Notification
and
Restart Notification
fields
before
submitting the form.