Fault isolation procedures
2
DS1 CONV system
Additional DS1-CONV loopback tests can further isolate the problem as shown in
Figure 2-18
.
Figure 2-18. DS1 CONV loopback tests
Figure 2-18
shows that:
■
If Test #799 fails at LB1, the problem is with DS1C #1, CSU #1, or the
connections between them.
■
If Test #799 passes at LB1 and fails at LB2, the problem is with CSU #1.
■
If Test #799 passes at LB1 and at LB2, the problem is with the DS1 facility,
CSU #2, connections to CSU #2, or DS1C #2.
■
For more information about loopback Tests #788 and #789 (isolates the
lightwave transceiver), see the DS1 CONV-BD section in Chapter 9 of
DEFINITY ECS Release 9 Maintenance for R9r
.