DEFINITY Enterprise Communication Server Release 9
Installation and Maintenance for Survivable Remote EPN
555-233-121
Issue 2
November 2000
SREPN Maintenance
2-27
Fault isolation procedures
2
9. If you find
none
of the errors in Step 7, then resolve any SNI-PEER errors.
a. If there is one SNI circuit pack with many different SNI-PEER error
types, replace the indicated SNI circuit pack
b. If there are many SNI-PEER errors of the same error type, replace
the indicted SNI circuit pack using
Table 2-10
.
c. After replacing an SNI circuit pack, clear alarms by executing test
board UUCSS long clear for all alarmed EXP-INTF circuit packs.
Wait 5 minutes for any SNI-BD or SNI-PEER alarms to clear.
NOTE:
You can speed this process with clear firmware counters [a-
pnc | b-pnc] for the repaired PNC.
10. Enter list fiber-link to get the physical location of the fiber-link endpoints.
11. If a DS1 CONV is administered to the fiber-link (DS1 CONV is
y
), enter
display fiber-link to determine the physical location of the DS1 CONV
circuit packs on the fiber-link.
Table 2-10.
SNI-PEER errors
Error Type
SNI slot
1
2
257
3
513
4
769
5
1025
6
1281
7
1537
8
1793
9
2049
13
2305
14
2561
15
2817
16
3073
17
3329
18
3585
19
3841
20
Continued on next page