AUX DC Inverter Free Match 50HZ
R32
Part7 Capacity Amendment
1. Operation range
Cooling capacity
(KBtu/h)
12K
18K
24K
30K
36K
42K
Power supply
220-240V~/50Hz
Voltage
187~242V
Ambient
temperature
Cooling
-15~52
℃
Heating
-15~24
℃
2. Capacity amendment of different ambient temperature
2.1 Amendment coefficient of Cooling capacity under different indoor/outdoor DB/WB
temperature
K1
IDU temp.
℃
Outdoor air inlet DB temperature
℃
DB
WB
-15
-10
0
10
16
25
30
35
40
43
48
52
23
16
1.26 1.19 1.12 1.08 1.05
1
0.95 0.90 0.87 0.85 0.82 0.77
25
18
1.28 1.26 1.19 1.12 1.08 1.05
1
0.95 0.90 0.87 0.85 0.82
27
19
1.30 1.28 1.26 1.19 1.12 1.08 1.05
1
0.95 0.90 0.87 0.85
28
20
1.33 1.30 1.28 1.26 1.19 1.12 1.08 1.05
1
0.95 0.90 0.87
30
22
1.5 1.33 1.30 1.28 1.26 1.19 1.12 1.08 1.05
1
0.95 0.90
32
24
1.7
1.5 1.33 1.30 1.28 1.26 1.19 1.12 1.08 1.05
1
0.95
Actual cooling capacity calculation:
Actual cooling capacity=amendment coefficient of cooling capacity × nominal cooling
capacity
——Rated cooling capacity could be found from
【
Part 4 Specification
】
——Amendment coefficient of cooling capacity could be found from table above.
Summary of Contents for AMWM-H07/4R3
Page 54: ...AUX DC Inverter Free Match 50HZ R32 3 Ceiling Floor 09K 12K 18K 929 660 245 841 205 ...
Page 57: ...AUX DC Inverter Free Match 50HZ R32 57 5 Outdoor Unit 5 1 14K 18K 545 800 545 822 315 315 ...
Page 58: ...AUX DC Inverter Free Match 50HZ R32 5 2 21K 27K 834 540 655 854 335 328 ...
Page 59: ...AUX DC Inverter Free Match 50HZ R32 59 5 3 36K 42K 985 675 808 1000 409 395 ...
Page 64: ...AUX DC Inverter Free Match 50HZ R32 3 Ceiling Floor 09k 12k 18k ...
Page 65: ...AUX DC Inverter Free Match 50HZ R32 65 4 Duct 07K 09K 12K 18K ...
Page 67: ...AUX DC Inverter Free Match 50HZ R32 67 5 1 36K 42K ...
Page 73: ...AUX DC Inverter Free Match 50HZ R32 73 Part8 Static pressure curve 1 07K 09K Duct ...
Page 74: ...AUX DC Inverter Free Match 50HZ R32 2 12K Duct ...
Page 75: ...AUX DC Inverter Free Match 50HZ R32 75 3 18K Duct ...
Page 81: ...AUX DC Inverter Free Match 50HZ R32 81 ...
Page 122: ...AUX DC Inverter Free Match 50HZ R32 5 3 2 1 4 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 ...
Page 135: ...AUX DC Inverter Free Match 50HZ R32 135 2 Cassette 09K 12K 18K ...
Page 139: ...AUX DC Inverter Free Match 50HZ R32 139 4 Duct 4 1 07K 09K 12K ...
Page 141: ...AUX DC Inverter Free Match 50HZ R32 141 4 2 18K ...
Page 143: ...AUX DC Inverter Free Match 50HZ R32 143 5 Outdoor Unit 5 1 14K 18K ...
Page 145: ...AUX DC Inverter Free Match 50HZ R32 145 ...
Page 147: ...AUX DC Inverter Free Match 50HZ R32 147 5 3 36K ...
Page 149: ...AUX DC Inverter Free Match 50HZ R32 149 5 4 42K ...
Page 155: ...AUX DC Inverter Free Match 50HZ R32 155 4 Cassette 4 1 Installation drawing ...
Page 160: ...AUX DC Inverter Free Match 50HZ R32 ...
Page 181: ...AUX DC Inverter Free Match 50HZ R32 181 1 2 21K 27K Main PCB and Driver modular ...
Page 182: ...AUX DC Inverter Free Match 50HZ R32 1 3 36K 42K Main PCB ...
Page 183: ...AUX DC Inverter Free Match 50HZ R32 183 Drive Modular Board ...
Page 184: ...AUX DC Inverter Free Match 50HZ R32 2 Indoor Unit PCB 2 1 09K 12K 18K Cassette ...
Page 185: ...AUX DC Inverter Free Match 50HZ R32 185 2 2 09K 12K 18K Ceilling Floor ...
Page 186: ...AUX DC Inverter Free Match 50HZ R32 2 3 07k 09K 12K 18K Duct ...
Page 191: ...AUX DC Inverter Free Match 50HZ R32 191 Outdoor protection phase sequence ...
Page 193: ...AUX DC Inverter Free Match 50HZ R32 193 2 4 H6 low pressure protection ...
Page 195: ...AUX DC Inverter Free Match 50HZ R32 195 2 5 P5 High exhaust temperature protection ...
Page 196: ...AUX DC Inverter Free Match 50HZ R32 Cooling exhaust temperature protection ...
Page 197: ...AUX DC Inverter Free Match 50HZ R32 197 Heating exhaust temperature protection ...
Page 198: ...AUX DC Inverter Free Match 50HZ R32 2 6 H8 four way valve failure protection ...
Page 199: ...AUX DC Inverter Free Match 50HZ R32 199 2 7 Sensor failure protection ...