AUTROFLAME IR-FLAME DETECTOR BG-21

Interactive fire detector systems 

Mounting instructions

Doc-1000336-2, 2021-05-19

Avoid static discharges when 

mounting the detector

Dimensions

119 x 63.5 mm

Distance between fixing holes: 100 mm

  

Glands 

suitable for cable size 6 – 12 mm. These 

must be used in order to maintain the degree of 

protection.

      

Wire: Max. 2.5 mm

2

 /14 AWG

Connection to the first detector in 

the loop and between detectors in 

the loop:

Terminal Connection

1

+ in

2

-in/out

3

+ out/alarm resistor

4

alarm resistor

Connection to the final detector in 

the loop or a single detector:

Terminal Connection

1

+ in

2

-in / EOL

3

alarm resistor / EOL

4

alarm resistor

Terminals

1  2  3  4 

 

Where a screened loop cable is required, use Thorix to connect the 

screen in/out of the detector. The screen should only be connected 

to the earth at one end (on the panel).

Connection