60
COMPACT VOICE ALARM SYSTEM
SERVICE MANUAL
7.3.2 Batteries
It is necessary to protect batteries from short-circuit while connecting battery leads. Short-circuit may lead to system failure.
Follow this manual to assure safety while connecting.
Make sure the system power has been switched off before battery is connected.
Once the batteries have been connected, make sure all terminals of all batteries have been protected against short-circuit.
Connecting batteries
» Wait over 10 seconds after the power cord was unplugged from AC socket located on the AutroVoice miniVES main unit.
» Never connect negative cable in the first place as in the case of short-circuit between battery positive wire and a device
frame or rack cabinet element, a device damage may occur.
» Connect battery negative cable to negative terminal.
Disconnecting batteries
» Make sure battery supply is not used. To do so, check LED on the AutroVoice miniVES front panel which signals such state of affairs.
» Take out battery negative lead from terminals. Never disconnect positive wire in the first place as it may cause short-circuit
if you touch device frame or rack cabinet elements. Isolate disconnected cable tip with a suitable insulator, e.g. insulating
tape, to protect against short-circuit.
» Disconnect last battery lead. Isolate disconnected wire tip with a suitable insulator, e.g. insulating tape, to protect
against short-circuit.
c
A total voltage of batteries connected to the device, loading and monitoring, according to EN 54-4 should reach 48 V DC
(40-56 V DC). In the last stage of system comissioning, it is necessary to connect four VRLA 12 V batteries to the battery port
located on the main connector panel of the AutroVoice miniVES unit via the provided cable with special regard to wire
polarity. Additionally, it is necessary to connect a thermistor temperature sensor by connecting its wire to Temp Sensor
connector and placing the sensor in the place where the batteries were installed.
Drawing 35.
4x12 V DC VRLA storage batteries connecting diagram
Summary of Contents for AutroVoice miniVES 2001
Page 2: ...2 COMPACT VOICE ALARM SYSTEM SERVICE MANUAL...
Page 6: ...6 COMPACT VOICE ALARM SYSTEM SERVICE MANUAL...
Page 147: ...147 15 Certificates...
Page 152: ...152 COMPACT VOICE ALARM SYSTEM SERVICE MANUAL Notes...
Page 153: ...153...
Page 154: ...154 COMPACT VOICE ALARM SYSTEM SERVICE MANUAL...
Page 155: ...155...