12.11 Basic steps required to program the system
In order to program a basic AutroVoice miniVES configuration and make the system fully operational, follow these steps:
1.
Logical output OUT1 – assign the
Error
event and change it’s generic name to
Fault
2. Logical output OUT2 – assign the
Alarm
mode event and change the generic name to
Alarm ACK
3. Add the alarm (evacuation) message and change it’s generic name to
Evacuation
. Set it’s priority to 10
4. Change the generic name of the Audio input no.3 to
Local Audio IN
5. Change the generic name of the built in firemans microphone (audio input no.1) to
Fire Mic minives XXXX
6. Change the generic name of the built in microphone in general mode (audio input no.2) to
Local Mic
7. On the line control cards, change the generic names:
Ű
miniVES2001
Zone 1 – lines A+B, Zone 2 – lines C+D, control method: impedance
Ű
miniVES4001
card in slot 1: Zone 1 – lines A+B, Zone 2 – lines C+D, control method: impedance
card in slot 2: Zone 3 – lines A+B, Zone 4 – lines C+D, control method: impedance
Ű
miniVES4002
card in slot 1: Zone 1 – lines A+B, Zone 2 – lines C+D, control method: impedance
card in slot 2: Zone 3 – lines A+B, Zone 4 – lines C+D, control method: impedance
card in slot 3: Zone 5 – lines A+B, Zone 6 – lines C+D, control method: impedance
card in slot 4: Zone 7 – lines A+B, Zone 8 – lines C+D, control method: impedance
8. Create a
Zone group
–
All Zones
and add all of the available zones depending on the AutroVoice miniVES type
9. Create a new matrix and name it
Evacuation
– add the Evacuation message from the available
Audio inputs
field
and the
All zones zone group
10. Logical input INPUT1, contact mode – assign the following events:
Ű
Active
–
Alarm
mode (start) and
Genera
l – add the
Evacuation
matrix (start)
Ű
Inactive
–
Alar
m mode (stop)
Change the generic name of the input to
Evac activation
.
11. In the
Events configuration
tab:
Ű Assign the built in
Emergency
buton (1) to Alarm mode event (start) and the select zone event choosing
All zones
Ű Key 2 – change the generic name to Evacuation Start and assign the start/stop matricing event (toggle)
Ű Key 3 – change the generic name to LED test and assign the led test event
Ű Key 4 – change the generic name to Stop Evacuation and assign the Alarm mode (stop)
Summary of Contents for AutroVoice miniVES 2001
Page 2: ...2 COMPACT VOICE ALARM SYSTEM SERVICE MANUAL...
Page 6: ...6 COMPACT VOICE ALARM SYSTEM SERVICE MANUAL...
Page 147: ...147 15 Certificates...
Page 152: ...152 COMPACT VOICE ALARM SYSTEM SERVICE MANUAL Notes...
Page 153: ...153...
Page 154: ...154 COMPACT VOICE ALARM SYSTEM SERVICE MANUAL...
Page 155: ...155...