Autonics TZN4H Instruction Manual Download Page 1

 

1: The weight includes packaging. The weight in parentheses is for unit only.

Environment resistance is rated at no freezing or condensation.

Theunitcannotbeconfiguredwithanyrandomcombinationfromtheaboveorderinginformation.Please

refer to 

Specificationsforpossibleconfigurations.

1:  TZN4S only supports Event 1 option output. 

Dual PID Control Temperature Controller

TZN SERIES

I N S T R U C T I O N   M A N U A L

Thank you for choosing our Autonics product.

Please read the following safety considerations before use.

 Safety Considerations

Pleaseobserveallsafetyconsiderationsforsafeandproperproductoperationtoavoidhazards.

Safety considerations are categorized as follows.

Warning

 Failure to follow these instructions may result in serious injury or death.

Caution 

Failure to follow these instructions may result in personal injury or product damage.

The symbols used on the product and instruction manual represent the following

 symbol represents caution due to special circumstances in which hazards may occur. 

Warning

 

 Ordering Information

TZN 4

S

1

4 R

Item

Digit

Size

Option output

Powersupply

Control 

output

R

Relay output

S

SSR drive output

C

Current output

4

100-240VAC 50/60Hz

1

1

Event 1

2

Event 1 + Event 2

R

PVtransmission(DC4-20mA)

T

Event 1 + RS485 communication

A

PVtransmission(DC4-20mA)

B

Event 1 + Event 2 + RS485 communication

S

DIN W48×H48mm

M

DIN W72×H72mm

W

DIN W96×H48mm

H

DIN W48×H96mm

L

DIN W96×H96mm

4

9999(4-digit)

TZN

Temperaturecontroller(PIDNewType)

 Specifications

Series

TZN4S

TZN4M

TZN4W

TZN4H

TZN4L

Powersupply

100-240VAC  50/60Hz

Allowable voltage range 90 to 110% of rated power voltage

Powerconsumption

Max.5VA(100-

240VAC50/60Hz) Max.6VA(100-240VAC50/60Hz)

Display method

7-segmentLED(PV:red,SV:green)

Character 

size

PV(W×H)

7.8×11.0 mm

8.0×13.0 mm

8.0×10.0 mm

7.8×11.0 mm

9.8×14.2 mm

SV(W×H)

5.8×8.0 mm

5.0×9.0 mm

5.8×8.0 mm

8.0×10.0 mm

Input 

type 

RTD

DPt100Ω,JPt100Ω,3-wire(allowedresistance:max.5Ωperline)

TC

K(CA),J(IC),R(PR),E(CR),T(CC),S(PR),N(NN),W(TT)

(allowedresistance:max.100Ωperline)

Analog

1-5VDC

,0-10VDC ,DC4-20mA

Display accuracy

F.S. ±0.3% or 3

,greatervalue

Control

output 

Relay 

250VAC  3A 1c 

SSR

Max. 12VDC  ±3V 30mA

Current

DC4-20mA(loadresistancemax.600Ω)

Option

output

EVENT1

250VAC  1A 1a

EVENT2

-

250VAC  1A 1a

PVtransmission

-

DC4-20mA

(loadresistancemax.600Ω)

Communication -

RS485 communication

Control method

ON/OFF,P,PI,PD,PIDF,PIDScontrol

Alarm output hysteresis 1 to 100

(0.1to100.0

)variable

Proportionalband(P)

0.0 to 100.0% 

Integraltime(I)

0to3,600sec

Derivativetime(D)

0to3,600sec

Controlperiod(T)

1 to 120 sec

Sampling period

0.5 sec

LBA setting

1 to 999 sec

Ramp setting

RampUp,RampDown:1to99mineach

Dielectric strength

2,000VAC50/60Hzfor1min(betweeninputandpowerterminals)

Vibration

Mechanical

0.75mmamplitudeatfrequency10to55Hz(for1min)ineachX,Y,Zdirectionfor2hours

Electrical

0.5mmamplitudeatfrequency10to55Hz(for1min)ineachX,Y,Zdirectionfor10min

Relay

life cycle

Control output

Mechanical:min.10,000,000operations,

Electrical:min.100,000operations(250VAC3Aresistanceload)

Option output

Mechanical:min.20,000,000operations,

Electrical:min.500,000operations(250VAC1Aresistanceload)

Insulation resistance

Over 100M

Ω(at500VDCmegger)

Noise immunity

Squareshapednoisebynoisesimulator(pulsewidth1

)±2kVR-phase,S-phase

Memory retention

Approx.10years(non-volatilesemiconductormemorytype)

Environ

ment

Ambient temp. -10 to 50

,storage:-20to60

Ambient humi.

35to85%RH,storage:35to85%RH

Approval

 

Weight

1

Approx. 226g

(approx.164g)

Approx. 355g

(approx.246g)

Approx. 351g

(approx.232g)

Approx. 474g

(approx.303g)

 Input Type and Range

 Configuring Input Type

Pleaseconfiguretheinternalswitchesbeforesupplyingpower.Aftersupplyingpower,configuretheinputtype

[

IN-T

] in parameter group 2 according to the input type. 

●Detachingthecase

Pressthefrontcasethenpullthecasetodetachthecasefromthebody.

Configuretheinternalswitchesasinputtype.

Input type

S/W 1

S/W 2

Thermocouple

1 1

mA V

RTD

Analog

Voltage

(0-10VDC,

1-5VDC)

2 2

mA V

Current

(DC4-20mA)

2 2

mA V

 Dimensions

 Connections

(unit:mm)

(unit:mm)

         Size
Series

A

B

C

D

TZN4S

Min. 55

Min. 62

45.5

+0.5

   0

45.5

+0.5

   0

TZN4M

Min. 91

Min. 91

68

+0.7

   0

68

+0.7

   0

TZN4W

Min. 112 Min. 50

92

+0.8

   0

45.5

+0.6

   0

TZN4H

Min. 50

Min. 102 45

+0.6

   0

92

+0.8

   0

TZN4L

Min. 98

Min. 106 91

+0.5

   0

91

+0.5

   0

●TZN4S

30

73

12

10

4

3.5

10

48

10

79.5

10.5

100

45

●TZN4M

10

72

73

83

67

●TZN4W

96

13

90

10

45

48

●TZN4H

48

13

90

10

90

96

AT

SV2

EV2

EV1

OUT

TEMPERATURE CONTROLLER

AT

MD

PV

SV

°C

●TZN4L

96

13

90

10

90

A

C

D

B

45.4

61

3.9

7.4

15

4.5

4.2

41

12.2

48

47.8

61

 TZN4S Series

TZN4M,TZN4W,TZN4H,TZN4LSeries

 Bracket

 Panel cut-out dimensions

●TZN4S

●TZN4M

●TZN4L

EV1 OUT

250VAC 1A 1a
EV2 OUT

250VAC 1A 1a

SV2 IN

Max.5VDC

250

B'

TC

RTD

SENSOR

B

A

-

+

MAIN OUT

SSR

Current

12VDC ±3V

30mA Max.

DC4-20mA

Load600ΩMax.

mA

V

-

-

+

+

15

14

15

14

MAIN OUT

250VAC 3A 1c

Resistive load

PVOUT

DC4-20mA

H

C

L

-

+

RS485(A+)

RS485(B-)

-

+

SOURCE

100-240VAC 

50/60Hz 6VA

●TZN4H

SOURCE

100-240VAC

50/60Hz 6VA

EV1 OUT

250VAC 1A 1a
EV2 OUT

250VAC 1A 1a

SV2 IN

Max.5VDC

250

MAIN OUT

250VAC 3A 1c

Resistive load

PVOUT

DC4-20mA

B'

TC

RTD

SENSOR

B

A

H

C

L

-

+

RS485(A+)

RS485(B-)

-

+

-

+

●TZN4W

EV1 OUT

250VAC 

1A 1a

EV2 OUT

250VAC 

1A 1a

SV2 IN

Max.5VDC

250

B'

RTD

TC

SENSOR

B

A

- +

SOURCE

100-240VAC

50/60Hz 6VA

MAIN OUT

250VAC 3A 1c

Resistive load

PVOUT

DC4-20mA

H

C

L

-

-

+

+

RS485

(A+)

RS485

(B-)

MAIN OUT

SSR

Current

-

+

V

3
2

12VDC ±3V

30mA Max.

-

+

3
2

mA

DC4-20mA

Load600ΩMax.

MAIN OUT

SSR

Current

-

+

V

7
6

12VDC ±3V

30mA Max.

-

+

7
6

mA

DC4-20mA

Load600ΩMax.

MAIN OUT

SSR

Current

-

+

V

15
14

12VDC ±3V

30mA Max.

-

+

15
14

mA

DC4-20mA

Load600ΩMax.

MAIN OUT

SSR

Current

-

+

V

15
14

12VDC ±3V

30mA Max.

-

+

15
14

mA

DC4-20mA

Load600ΩMax.

SOURCE

100-240VAC

50/60Hz 5VA

EV1 OUT

250VAC

1A 1a

SV2 IN

Max.5VDC

250

MAIN OUT

250VAC 3A 1c

Resistive load

B'

RTD

TC

SENSOR

B

A

H

C

L

+

-

-

+

EV1 OUT

250VAC 1A 1a
EV2 OUT

250VAC 1A 1a

SV2 IN

Max.5VDC

250

MAIN OUT

250VAC 3A 1c

Resistive load

PVOUT

DC4-20mA

SOURCE

100-240VAC 50/60Hz 6VA

H

RS485(A+)

RS485(B-)

C

L

-

-

-

+

+

+

B'

RTD

TC

SENSOR

B

A

-
+

DRW170714AA

Caution

1.  Fail-safe device must be installed when using the unit with machinery that may cause serious injury 

or substantial economic loss. (e.g. nuclear power control, medical equipment, ships, vehicles, 

railways, aircraft, combustion apparatus, safety equipment, crime/disaster prevention devices, etc.)

 

Failuretofollowthisinstructionmayresultinfire,personalinjury,oreconomicloss.

2.  Install on a device panel to use.

 

Failure to follow this instruction may result in electric shock.

3.  Do not connect, repair, or inspect the unit while connected to a power source.

 

Failuretofollowthisinstructionmayresultinelectricshockorfire.

4.  Check 'Connections' before wiring.

 

Failuretofollowthisinstructionmayresultinfire.

5.  Do not disassemble or modify the unit.

 

Failuretofollowthisinstructionmayresultinelectricshockorfire.

1.   When connecting the power input and relay output, use AWG 20(0.50mm

2

) cable or over and tighten 

the terminal screw with a tightening torque of 1.0N.m.  

When connecting the sensor input and communication cable without dedicated cable, use AWG 

28~16 cable and tighten the terminal screw with a tightening torque of 1.0N.m.

 

Failuretofollowthisinstructionmayresultinfireormalfunctionduetocontactfailure.

2.  Use the unit within the rated specifications.

 

Failuretofollowthisinstructionmayresultinfireorproductdamage.

3.  Use dry cloth to clean the unit, and do not use water or organic solvent. 

Failuretofollowthisinstructionmayresultinelectricshockorfire.

4.  Do not use the unit in the place where flammable/explosive/corrosive gas, humidity, direct sunlight, 

radiant heat, vibration, impact, or salinity may be present.

 

Failuretofollowthisinstructionmayresultinfireorexplosion.

5.  Keep metal chip, dust, and wire residue from flowing into the unit.

 

Failuretofollowthisinstructionmayresultinfireorproductdamage.

 The above specifications are subject to change and some model may be discontinued 

without notice.

Be sure to follow cautions written in the instruction manual and the technical descriptions 

(catalog, homepage).

Input type

Decimal point Display

Inputrange(

)

Inputrange(

)

Thermo 

couple

K(CA)

1

KCaH

-100 to 1300

-148 to 2372

K(CA)

0.1

KCaL

-100.0 to 999.9

Not supported

J(IC)

1

JIcH

0 to 800

32 to 1472

J(IC)

0.1

JIcL

0.0 to 800.0

Not supported

R(PR)

1

R  PR

0 to 1700

32 to 3092

E(CR)

1

ECrH

0 to 800

32 to 1472

E(CR)

0.1

ECrL

0.0 to 800.0 

Not supported

T(CC)

1

TCcH

-200 to 400

-328 to 752

T(CC)

0.1

TCcL

-199.9 to 400.0

Not supported

S(PR)

1

S  PR

0 to 1700

32 to 3092

N(NN)

1

  NN

0 to 1300

32 to 2372

W(TT)

1

U TT

0 to 2300

32 to 4172

RTD

JPt100Ω

1

JPtH

0 to 500

32 to 932

JPt100Ω

0.1

JPtL

-199.9 to 199.9

-199.9 to 391.8

DPt100Ω

1

DPtH

0 to 500

32 to 932

DPt100Ω

0.1

DPtL

-199.9 to 199.9

-199.9 to 391.8

Analog

Voltage

0 - 10VDC 

A--1

-1999 to 9999

(displayrangewillvarydependingonthe

 

decimalpoint.)

1 - 5VDC 

A--2

Current

DC4 - 20mA

A--3

a b

<Round>

a b

<Forked>

a

Min. 3.5mm

Min. 3.5mm

b

Max. 7.2mm

Max. 7.2mm

Useteminalsofsizespecifiedbelow.