2 Modbus Mapping Table
© Copyright Reserved Autonics Co., Ltd.
23
2.4.4
Parameter 2 Setting Group
No(Address)
Parameter Description
Setting range
Factory
default Unit
Note
400151(0096)
OFT
Compressor output mode
0:
C
, 1:
H
0
-
400152(0097)
HYS
Hysteresis
1
to
5
(
)5
to
%0
)
1
℃
2
to
10
(
@0
to
1)0
)
℉
400153(0098)
OFS
Offset
0
to
5
(
)0
to
%0
)
0
℃
0
to
10
(
)0
to
1)0
)
℉
400154(0099)
HSV
SV high limit value
(SV low limit +1 digit) to
high limit value of input
type
99
℃
/
℉
400155(009A)
LSV
SV low limit value
Low limit value of input
type to
(SV high limit -1 digit)
-40
℃
/
℉
400156(009B)
nMD
Night mode
0:
OFF
, 1:
TIM
, 2:
DI
0
℃
/
℉
400157(009C)
nSV
Night mode SV correction
-20
to
20
(
-20
to
2)0
)
1
℃
-50
to
50
(
-50
to
5)0
)
℉
400158(009D)
nHY
Night mode hysteresis
1
to
5
(
)5
to
%0
)
1
℃
2
to
10
(
@0
to
1)0
)
℉
400159(009E)
nOF
Night mode offset
0
to
5
(
)0
to
%0
)
0
℃
0
to
10
(
)0
to
1)0
)
℉
400160(009F)
NSH
Night mode start hour
0
to
23
0
Hour
400161(00A0)
NSM
Night mode start min
0
to
59
0
Min
400162(00A1)
NEH
Night mode end hour
0
to
23
8
Hour
400163(00A2)
NEM
Night mode end min
0
to
59
0
Min
400164(00A3)
eMO
Temperature monitoring
0:
OFF
, 1:
S1
, 2:
S2
,
3:
S3
, 4:
VS
0
-
400165(00A4)
SDL
Compressor start-up delay time
0
to
60
0
Min
400166(00A5)
CYC
Compressor min. operation cycle
0
to
60
0
Min
400167(00A6)
RDL
Compressor restart delay time
0
to
60
0
Min
400168(00A7)
ONT
Compressor min. operation time
0
to
60
0
Min
400169(00A8)
CC
Compressor continuous operation
0
to
24
0
Hour
400170(00A9)
AdC
Alarm delay time after continuous
operation
0
to
24
2
Hour
400171(00AA)
CLE
Compressor operation cylce when
sensor break
0
to
100
0
Min
400172(00AB)
DUT
Compressor duty rate when sensor
break
0
to
100
50
%
400173 to
400250
Reserved
Summary of Contents for TF3 Series
Page 1: ...Preface Copyright Reserved Autonics Co Ltd 1 USER MANUAL For COMMUNICATION ...
Page 2: ...Preface 2 Copyright Reserved Autonics Co Ltd ...
Page 28: ...2 Modbus Mapping Table 28 Copyright Reserved Autonics Co Ltd ...
Page 29: ...2 Modbus Mapping Table Copyright Reserved Autonics Co Ltd 29 MCT TF3C1 V1 1 1701US ...