background image

K-78

LE7M-2

 Ordering Information

 Specifications

W72×H72mm, Weekly/Yearly Timer

● Easy to check and change the program setting

● Customizable weekly or yearly unit time setting

   and control by user

● Includes daylight saving time function

● Built-in 2 independent control output (relay)

● Flush and surface mounting are in one unit

● Enable to mount on DIN rail with base plate

Model

LE7M-2 

Power supply

100-240VAC 50/60Hz

Allowable voltage range

90 to 110% of rated voltage

Power consumption

Max. 4.2VA (100-240VAC 50/60Hz)

RETURN input

Short-circuit or open by switch or relay

Timing program

48 steps for weekly, 24 steps for yearly

Operation mode

ON/OFF mode, cycle mode, pulse mode

Mounting

Front panel, surface, DIN rail

Time deviation

±15sec./month (ambient temperature: 25

) (±4sec. /week)

Temperature error

±0.01% ±0.05sec. (ratio by set time)

Memory protection

Over 5 years (at 25

)

Control

Output

Contact type

SPDT (Single Pole Double Throw)

Contact capacity

250VAC 10A resistive load

Output number

Independent 2 output (1c × 2)

Relay

life cycle

Mechanical

Min. 5,000,000 operations (switching capacity: 30 times/min)

Electrical

Min. 50,000 operations<switching capacity: 20 times/min, 250VAC 10A (resistive load)>

Insulation resistance

Min. 100MΩ (at 500VDC megger)

Dielectric strength

2000VAC 50/60Hz for 1minute

Noise strength

±2kV the square wave noise (pulse width: 1

) by the noise simulator

Environment

Ambient temperature -10 to 55

, storage: -25 to 65

Ambient humidity

35 to 80%RH

Unit weight

Approx. 272g

Item

Size

Output

LE7

M

2

2

2 Relay outputs

M

DIN W72×H7mm

LE7

Weekly/Yearly timer

 Features

Environment resistance is rated at no freezing or condensation.

   

Please read “Caution for your safety” in operation 

manual before using.

Summary of Contents for LE7M-2

Page 1: ...temperature 25 4sec week Temperature error 0 01 0 05sec ratio by set time Memory protection Over 5 years at 25 Control Output Contact type SPDT Single Pole Double Throw Contact capacity 250VAC 10A res...

Page 2: ...RCE SOURCE Single phase Three phase COM COM COM COM N O N O N O Power of single phase Load Load Magnetic Switch Magnetic Switch Power of three phase N O RETURN INPUT CONTACT OUT 250VAC 10A RESISTIVE L...

Page 3: ...then rotate it 180 degree Assemble terminal block to case by using the 4 bolts Dimensions Mounting How To Switch From The Flush Mounting To Surface Mounting Type unit mm 68 0 7 0 68 0 7 0 Remove termi...

Page 4: ...ain display 13 Remaining step display 14 Operation mode display 15 Power restore input display 16 Output mode display 17 Year month date display 18 Unit of pulse width display 19 Sub display 20 CHECK...

Page 5: ...ower restore input is detected RET IN turns off and output operates according to program Power restore input Input contact signal in external Return input terminals to by switch or relay or press key...

Page 6: ...matic Daylight Saving Time mode and press key But the minute will be fixed as 00 Normal NOR daylight saving time mode Press key over 3sec in RUN mode 1h turns ON and current time is faster as an hour...

Page 7: ...flash Program 1 yearly program setting Program 2 yearly program setting All Program 1 weekly program delete All Program 2 weekly program delete All Program 1 yearly program delete All Program 2 yearl...

Page 8: ...g Press key to move the indicator to monday it will be lighted when or key are pressed and move it to tuesday by key Press SET key after tuesday wednesday thursday friday turn ON SUN MON TUE WED THU F...

Page 9: ...r 10min OFF for 5min Weekly cycle mode E g Output 1 OUT1 is ON for 10min and OFF for 5min from monday 6 00AM to saturday 5 30PM SUN MON TUE WED THU FRI SAT Advance to program 1 P1 weekly program setti...

Page 10: ...early holiday setting SUN MON TUE WED THU FRI SAT Press MODE key to finish the additional yearly holiday setting and press SET key to set It is able to set yearly holiday up to 12 times Complete to ye...

Page 11: ...ion by key SUN MON TUE WED THU FRI SAT OFF time setting Hour Minute Move the flashing to minute position after set 5 00 by or key and set the minute as 10 and press SET key SUN MON TUE WED THU FRI SAT...

Page 12: ...display part press SET key It returns to check mode when finish the modify same as the above procedure 2 Program record delete When press SET key over 3sec in program check EDT flashes in second disp...

Reviews: