1 Modbus RTU protocol
10
© Copyright Reserved Autonics Co., Ltd.
1.2
Read Input Status(Func 02–02H)
Reads Input ON/OFF status(1X reference) in Slave device.
(1)
Query (Master)
Slave Address Function
Starting Address
No. of Points
Error Check(CRC16)
Hi(Upper)
Lo(Lower)
Hi(Upper)
Lo(Lower)
Lo(Lower)
Hi(Upper)
1Byte
1Byte
1Byte
1Byte
1Byte
1Byte
1Byte
1Byte
(2)
Response (Slave)
Slave Address Function
Byte Count
Data
(Data)
Data
(Data)
Data
(Data)
Error Check(CRC16)
Lo(Lower)
Hi(Upper)
1Byte
1Byte
1Byte
1Byte
1Byte
1Byte
1Byte
1Byte
If reading the input status(ON: 1, OFF: 0) of 10 range 100001(0000 H)to100010(0009 H)in the
Slave(Address 17) from the Master.
Query (Master)
Slave Address Function
Starting Address
No. of Points
Error Check(CRC16)
Hi(Upper)
Lo(Lower)
Hi(Upper)
Lo(Lower)
Lo(Lower)
Hi(Upper)
11 H
02 H
00 H
00 H
00 H
0A H
## H
## H
If the values range 100008(0007 H) to 100001(0000 H) on slave are “ON-ON-OFF-OFF-ON-ON-
OFF-ON”, and the values of 100010(0009 H) to 100009(0008 H) are respectively “OFF-ON”.
Response (Slave)
Slave Address Function
Byte Count
Data
(100008 to 100001)
Data
(100010 to 100009)
Error Check(CRC16)
Lo(Lower)
Hi(Upper)
11 H
02 H
02 H
CD H
01 H
## H
## H
CRC16
CRC16
Summary of Contents for BFC Series
Page 1: ... Copyright Reserved Autonics Co Ltd i USER MANUAL For COMMUNICATION ...
Page 2: ...ii Copyright Reserved Autonics Co Ltd ...
Page 8: ...Table of Contents viii Copyright Reserved Autonics Co Ltd ...
Page 45: ...2 Modbus Mapping Table Copyright Reserved Autonics Co Ltd 45 ...
Page 46: ...2 Modbus Mapping Table 46 Copyright Reserved Autonics Co Ltd MSB BFCC1 V1 3 1701US ...