background image

1                                                                     2 

 

DIGITAL INSULATION TESTER 

INSTRUCTION MANUAL 

 
   
   
 
 
 
 
 
 
 
 
 
 
 
 
 

SAFETY INFORMATION 

 

Read the following safety information carefully before 
attempting to operate or service the meter. 

 

To avoid damages to the instrument do not apply the 
signals which exceed the maximum limits shown in the 
technical specifications tables. 

 

Do not use the meter or test leads if they look damaged. 
Use extreme caution when working around bare 
conductors or bus bars. 

 

Accidental contact with the conductor could result in 
electric shock. 

 

Use the meter only as specified in this manual; 
otherwise, the protection provided by the meter may be 
impaired. 

 

Read the operating instructions before use and follow 
all safety Information. 

 

Caution when working with voltages above 60V DC or 
30V AC RMS. Such voltages pose a shock hazard. 

 

Before taking resistance measurements or testing 
acoustic continuity, disconnect circuit from main power 
supply and all loads from the circuit. 

 
 

 

Summary of Contents for ET2134

Page 1: ...Use extreme caution when working around bare conductors or bus bars Accidental contact with the conductor could result in electric shock Use the meter only as specified in this manual otherwise the protection provided by the meter may be impaired Read the operating instructions before use and follow all safety Information Caution when working with voltages above 60V DC or 30V AC RMS Such voltages ...

Page 2: ...riodically wipe the case with a dry cloth Do not use abrasives or solvents on this instruments Display Large LCD with dual display Measurement Range 200Ω 200kΩ 200MΩ 250V 200MΩ 500V 2000MΩ 1000V 750V ACV 1000V DCV Sampling Rate 2 5 times per second Zero Adjustment Automatic adjustment Over Range Indicator Number 1 of highest digit is displayed Low Battery Indication The is displayed when the batte...

Page 3: ...40Ω 4 5V 250Vrms Short circuit current 200mA DC Voltage Range Resolution Accuracy Input Impedance Overload Protection 1000V 1V 0 8 3 10MΩ 1000Vrms AC Voltage 40Hz 400Hz Range Resolution Accuracy Input Impedance Overload Protection 750V 1V 1 2 10 10MΩ 750Vrms Meg OHMS Range Resolution Accuracy Terminal Voltage 200MΩ 250V 0 1MΩ 3 5 250V 10 0 200MΩ 500V 0 1MΩ 500V 10 0 0 1000MΩ 1000V 1MΩ 1000V 10 0 1...

Page 4: ... of 6 pcs new batteries type 1 5V size AA is Required b Place back the battery cover and four the screws 3 3 Test leads check Set the range select switch to the 200Ω range With the tip and alligator clip of the test leads connected The indicator should read 00 0Ω When the leads are not connected the display will read infinity indicated by 1 This will ensure that test lead are under working conditi...

Page 5: ...V and then proceed as indicated in a above for 500V testing The above note also applies to testing at 1000V In addition the following applies Note Make sure that the circuit under does not include components Which will be damaged by the 1000V applied Many normal components of an installation are likely to be damaged if tested at 1000V Examples are power factor correction capacitors low voltage min...

Page 6: ...l include the resistance of the motor wire and all other components between the motor and the main switch If a weakness is in dicated the motor and other components should be checked individually If the motor is disconnected at the motor terminals connect one megohmmeter lead to the grounded motor housing and the other lead to One of the motor leads DC Disconnect the motor from the line To test th...

Page 7: ...e from other equipment Check each conductor to ground and or lead sheath by connecting one megohmmeter lead to a ground and or lead sheather and the other megohmmeter lead to each of the conductors in turn Check insulation resistance between conductors by connecting megohmmeter leads to conductors in pairs ...

Reviews: