C0-08TR-3 CLICK Expansion I/O Module
Copyright© 2020,
Automationdirect.com
Incorporated/All Rights Reserved Worldwide
Installation and Mounting
Safety Installation
Please heed the following instructions when
installing:
• Mount the CLICK PLC unit horizontally to provide
proper ventilation.
• Do not mount the CLICK PLC unit upside down, on
a horizontal surface, or in a vertical arrangement.
• There is a minimum clearance requirement of 2in.
(51mm) from all sides of the cabinet and the equipment.
• There is a minimum clearance requirement of 3in.
(76mm) from the wiring ducts and the equipment.
• Please use this product in a metal enclosure/cabinet.
Installing Expansion I/O Modules:
• Remove protective cover over buss port.
• Push the LOCK slide (top and bottom of modules) to “UNLOCK”.
• Align module pins and tabs (attachment of modules) into adjacent
slots and firmly push together.
• Push the LOCK slides to “LOCK” to lock modules rigidly together.
Additional Help and Support
• For additional technical support and questions, call our
Technical Support team @ 1-800-633-0405 or 770-844-4200
Air
Flow
TX
2
PORT
2
PORT
1
RX
2
RX
1
TX
1
PWR
ER
R
RU
N
ST
OP
RU
N
To remove an I/O module, first disconnect all phases of external
power source and wait
5 seconds
before installing or removing the
expansion I/O module of a functioning system.
Then push LOCK slides to “UNLOCK” and gently separate modules.
1. Safety Installation, Wiring or Handling
• Discharge static electricity before installation or wir-
ing in order to avoid electric equipment damage.
2. Preface
• CLICK C0-08TR-3 is supported by CLICK Programming software Ver 2.60
or higher.
3. Compliant Crimp-type terminal
• I/O terminals
4. The following crimping ferrules are recommended for 24VDC
terminal and I/O terminals of CPU and Expansion I/O.
5. Safety Standard
• To comply with safety standards, please observe and use the following:
Please use SELV (as defined by UL61010-2-201) and Limited Energy (as
defined by UL61010-1, 9.4)
Please ensure basic insulation is provided between each relay block.
In order to comply with IEC/UL 61010-2-201 if the output is connected
to a circuit lower than 30V, please provide an external isolation before
the relay output terminals. Basic isolation requires an air separation of at
least 1.5 mm, a creepage distance of at least 2.5 mm, and a withstand
voltage of 1500V rms.
Enclosures
It is important to select the appropriate enclosure to ensure safe and proper oper-
ation of your CLICK PLC system. Control applications vary and yours may require
additional considerations. At a minimum your enclosure should include:
• Conformance to electrical standards
• Protection from the elements in an industrial environment
• Common ground reference
• Maintenance of specified ambient temperature
• Access to equipment
• Security or restricted access
• Sufficient space for proper installation and maintenance of equipment
CAUTION
• When installing modules and CPU on DIN rails, always
use end brackets on both ends of assembly.
• You should use 35mm width DIN Rails.
• You should use M4 size screws when you surface mount.
• You should tighten the screws with a spring washer and
a small round washer and torque (0.5 to 0.6 N·m).
CAUTION
Do not operate without first installing safety cover over power supply
leads.
Company
Series
Model No.
Compliant Wire
Fröhlich
Twin Ferrules
V30AE001134
* 0.5 mm
2
(20 AWG)
* Rated torque is 0.5 N·m. Take care not to contact adjacent terminal.
51mm
Minimum clearance requirement
of 51mm for A, B, and C.
1
2
3
Locking Tabs (Top and Bottom)
OPEN
CLOSED
Modules easily connect to each other.