Part Number Key

AutomationDirect.com (ADC)

3505 Hutchinson Road, Cumming, GA 30040

Phone: (800) 633-0405 or (770) 889-2858

ACS035/ACS400 

SERIES

INSTALLATION 

INSTRUCTIONS

Quick Start Guide

1.  Route monitored wire through aperture.

2.  Mount the sensor to a DIN rail or panel.

3.  Connect power supply and output wiring. 

a. Use 30-12 AWG copper wire  and tighten termi-

nals to 7 in-lbs torque. 

b. Ensure supply power and load matches that 

shown on sensor label.

4.  

Adjust setpoints. 

a. Use trip adjust potentiometers to select 

setpoints. 

b. LED shows Green with power supply 

connected, Amber when the current has 

exceeded the setpoint. 

®

ACTS - Inst - Rev 1     0820 

P-N 394000024

Specifications

Power Supply

24VAC/DC ( +/- 8.3%)

Power Consumption

< 2VA

Output

(2) Independent Single Pole, Double Throw mechanical 

Relays

Contact Rating

1A @ 120VAC, 2A @ 30VDC

Response Time

40 - 120ms

Hysteresis

4% of setpoint

Setpoint Ranges

2-35 Amps (ACS035)

25-400 Amps (ACS400)

Setpoint Adjust

Two 3/4-turn potentiometers

Sensed Current  

Limit

1.1x range continuous

3x range for 6 seconds

5x range for 1 second

Isolation Voltage

UL508, UL tested to 1240VAC

Frequency Range

40-65 Hz

Sensing Aperture

1.31 in (33.3 mm) dia.

Environmental 

-Temp -4 to 122°F (-20 to 50°C)

-Humidity 0-95% RH, Non-condensing

-Pollution degree 2

-Altitude 2000 meters

Case

UL 94V-0 Flammability rated thermoplastic

Certifications

cULus listed E222847

CE

 

 

 

A C S 035 - 2C - 24 -  F

SENSOR TYPE

ACS AC current operated switch

OUTPUT 

CASE STYLE

 

2C - (2) SPDT relay outputs, 

         independant setpoints

RANGE

035 - 2-35 Amps AC

400 - 25-400 Amps AC

POWER SUPPLY

24 - 24 VAC/DC

F - Fixed Core

Warning! Risk of electric shock or 

personal injury

Safe operation can only be guaranteed if the 
device is used for the purpose for which it was 
designed and within the limits of the technical 
specifications. When this symbol is used, it 
means you should consult all documentation to 
understand the nature of potential hazards and 
the action required to avoid them.

Warning! Risk of hazardous voltage

When operating the device, certain parts may 
carry hazardous live voltage (e.g., primary 
conductor, secondary terminals). The device 
should not be put into service if the installation is 
not complete.

For products intended for the EU market, the 

following is applicable to the CE compliance of 

the product:

The ACS035/ACS400 Series may comply with EN 61010-1 
CAT III 300V max line-to-neutral measurement category. If 
insulated cable is used for the primary circuit, the voltage rating 
of the measurement category can be improved according to 
the characteristics given by the cable manufacturer. 
Use 24V input power and fuse at 5 amps. Power source 
overvoltage category I as defined per EN 61010-1.

Part No. ACS035-2C-24-F