Chapter 1: Getting Started
Page 1–8
S
tride
®
MB Gateway User Manual
–
1st Edition Rev. E – August 2020
Wiring
Power
The switch can be powered from the same DC source that is used to power your other devices. To
maintain the UL listing, this must be an SELV (Safety Extra Low Voltage) power supply. A DC voltage
in the range of 12 to 48VDC needs to be applied between the P1+ terminal and the P1- terminal
as shown below. The chassis screw terminal should be tied to panel or chassis ground. To reduce
down time resulting from power loss, the switch can be powered redundantly with a second
power supply as shown below. A recommended DC power supply is AutomationDirect.com part
number PSL-24-010.
Terminal block connector is Degson 2EDGK-5.08-04P-14-1000AH or equivalent.
Ferrule required for stranded wire.
Wire Size Range: 24 – 12 AWG
Wire Strip Length: 7mm
Maximum terminal screw torque is
4.43 lb-in (0.5 N·m).
Redundant DC Power
Chassis
GND
(panel)
Optional Dual DC Supplies
P1+ P2-
P1-
P2+
– + – +
b
efoRe
peRfoRmING
ANy
WIRING
to
these
sWItches
mAke
suRe
...
• t
he
AReA
Is
cuRReNtly
NoNhAzARdous
(
especIAlly
WheN
WoRkING
IN
c
lAss
1, d
Iv
2
oR
z
oNe
2
hAzARdous
locAtIoNs
).
• p
oWeR
Is
off
to
the
sWItch
• t
he
scReW
teRmINAl
block
Is
uNpluGGed
. t
hIs
Is
especIAlly
ImpoRtANt
due
to
the
AlumINum
housING
. c
oNNectING
oR
dIscoNNectING
WIRes
to
the
scReW
block
WheN
It
’
s
IN
plAce
ANd
poWeR
Is
tuRNed
oN
cAN
AlloW
the
scReWdRIveR
to
shoRt
the
poWeR
to
the
cAse
.