Page 3–86
Stellar
®
SR55 Series Soft Starter User Manual – 1st Ed, Rev F – 09/18/2019
Chapter 3: Configuration and Parameters
f
AIl
s
Afe
c
odes
m
ain
b
oard
T
rip
(2402 – 2436)
A trip number in the range of 2402 to 2436 indicates that a process on the main board has
been affected in some way and is unable to recover automatically.
•
The trip is turned ON and OFF via the “Main Board Trip” (Advanced / Trips)�
•
The default for this trip is ON�
•
The trip MUST be reset using the either the digital input, touchscreen, or bus command
depending on the Control Method set�
•
As this is a special case, it is NOT possible to reset this trip by cycling the control supply�
Fail Safe Codes Associated with the Main Board
Code # Description
2402
Initialization process has been unsuccessful�
2404
Initialization of the Parameters has been unsuccessful�
2406
Initialization of the Overload has been unsuccessful�
2408
Initialization of the Parameter Read has been unsuccessful�
2410
Initialization of the Overload Read has been unsuccessful�
2412
Initialization of the Current measurement has been unsuccessful�
2420
A main process on the Main Board has been affected and is unable to recover automatically�
2422
A main process on the Main Board has been affected and is unable to recover automatically�
2424
A main process on the Main Board has been affected and is unable to recover automatically�
2426
Communication between the Main Board and Touchscreen Board has been affected and is unable to recover
automatically�
2428
The modbus communication has been affected and is unable to recover automatically�
2430
The parameter save has been unsuccessful�
2432
The logging function has been unsuccessful�
2434
A main process on the Main Board has been affected and is unable to recover automatically�
2436
The Anybus communication has been affected and is unable to recover automatically�
T
ouChsCreen
T
rip
(2501 – 2581)
A trip number in the range of 2501 to 2581 indicates that a process on the touchscreen board
has been affected in some way and is unable to recover automatically.
•
The trip is turned ON and OFF via the “Touchscreen Trip” (Advanced / Trips)�
•
The default for this trip is OFF�
•
With the trip OFF the touchscreen display may display the ‘start up’ screen momentarily as it
recovers automatically�
•
When the trip is turned ON it is reset using the either the digital input or touchscreen or bus
command, depending on the Control Method set�
•
It is possible to reset this trip by cycling the control supply�
Fail Safe Codes Associated with the Touchscreen Board
Local Touchscreen Code Remote Touchscreen Code Description
2501 – 2529
2551 – 2579
A main process on the Touchscreen Board has been
affected�
2530
2580
Communication between the Main board and Touchscreen
Board has been affected�
2531
2581
The touchscreen has become unresponsive�
When a remote touchscreen is used the same trips can be generated. However, to discriminate
between the remote and local (built in) 50 is added to each code.
Summary of Contents for Stellar SR55 Series
Page 1: ...Stellar SR55 Soft Starter User Manual SR55_UMW First Edition Revision F...
Page 2: ...Stellar SR55 Series Soft Starter User Manual 1st Ed Rev F 09 18 2019 BLANK PAGE...
Page 6: ...Page W 4 Stellar SR55 Series Soft Starter User Manual 1st Ed Rev F 09 18 2019 BLANK PAGE...
Page 8: ...Page H 2 Stellar SR55 Series Soft Starter User Manual 1st Ed Rev F 09 18 2019 BLANK PAGE...
Page 201: ...Stellar SR55 Series Soft Starter User Manual 1st Ed Rev F 09 18 2019 BLANK PAGE...
Page 202: ...Stellar SR55 Series Soft Starter User Manual 1st Ed Rev F 09 18 2019...