20
SR35 Quick-Start Guide
Stellar® SR35 Series Soft Starter Quick Start Guide – 1st Ed – 07/09/2020
e
leCTromagneTIC
C
ompaTIbIlITy
Electromagnetic Compatibility
EMC Emission levels
EN 55011
Class A
1)
EMC Immunity levels
IEC 61000-4-2
8kV/air discharge or 4kV/contact discharge
IEC 61000-4-3
10 V/m
IEC 61000-4-4
2kV/5kHz (main and power ports)
1kV/5kHz (signal ports)
IEC 61000-4-5
2kV line-to-ground
1kV line-to-line
IEC 61000-4-6
10V
1) NOTICE: This product has been designed for environment A. Use of this product in
environment B may cause unwanted electromagnetic disturbances, in which case the user
may be required to take adequate mitigation measures.
f
an
o
pTIon
Fan Option
SR35 Model
Maximum Duty Cycle F-S with Optional Fan Fitted
SR35-017 to SR35-100
90-40 (40 cycles per hour)
SR35-125
90-30 (30 cycles per hour)
SR35-156
90-20 (20 cycles per hour)
SR35-192
90-10 (10 cycles per hour)
SR35-242 – SR35-361 have permanently fitted fans.