DPM1-P User Manual, 1st Edition

User Manual - DPM1-P  Series Panel Meters

19

Activating mode selection: 

Lo: Low level activation 

Hi: High level activation 

CnF 

dLy

 

HyS

 

88

 

 

8888

 

      Lo 

      Hi

 

Pro 

Setpoint 1 configuration block 

Delay / Hysteresis selection 

Delay: from 

0

 to 

99s

 

Hysteresis:  

From 

0000

 to 

9999 

points 

of display. 

Stor 

Set

 

Activating mode selection: 

Lo: Low level activation 

Hi: High level activation 

CnF 

dLy

 

HyS

 

88

 

 

8888

 

      Lo 

      Hi

 

Setpoint 2 configuration block 

Delay / Hysteresis selection 

Delay: from 

0

 to 

99s

 

Hysteresis:  

From 

0000

 to 

9999 

points 

of display. 

Summary of Contents for ProSense DPM1-P Series

Page 1: ...es Digital Panel Meter Frequency Tachometer Rate Modes Models User Manual DPM1 P A2R H DPM1 P A2R L Scan or click the QR code for a series of Configuration and Programming videos for the ProSense DMP...

Page 2: ...iption 5 Dimensions and Mounting 6 Installation 6 Wiring Terminals 7 Input Wiring Diagrams 8 Programming Keys 9 Configuration 9 Programming numerical values 10 Input Configuration 11 Operation Mode Co...

Page 3: ...ste of electrical and electronic equipment from products put on the market after August 13 2005 the user can give it back without any cost to the place where it was acquired to proceed to its controll...

Page 4: ...est in the industry We rely on your feedback to let us know if we are reaching our goal If you cannot find the solution to your particular application or if for any reason you need technical assistanc...

Page 5: ...voltages The meter is powered from an external AC or DC power supply The 1 32 DIN housing takes up minimal panel space and the meter face has an IP65 rating Configuration parameters can be locked out...

Page 6: ...While holding the unit in place put the fixing clip around the case and slide it until it reaches the panel at the rear side Press slightly to fasten the clips to the latching slots on the case and ge...

Page 7: ...102 Wago 231 102 026 000 Wago 231 302 026 000 Cage clamp connection Insertion tool or screwdriver with 0 5 mm x 3 0 mm blade Insertion tool or screwdriver with 0 3 mm x 1 8 mm blade Insertion tool or...

Page 8: ...g device To guarantee electromagnetic compatibility the following guidelines should be kept in mind Power supply wires should be separately routed from signal wires and never run in the same conduit U...

Page 9: ...uration if present A out Press ENTER to access the submenus under each programming menu If configuration has been totally locked out when pressing ENTER to access the main menu level the display shows...

Page 10: ...e type A variable that represents the value of an input will be able to take a value in the range 0 to 9999 without taking into account the decimal point When a digit is selected it shows values from...

Page 11: ...itched contact 5 6 7 E 12 U 8 U 5 U Pro InP ModE SEt 1 2 3 4 Operation mode config Setpoints configuration Stor Pro A out Analog output configuration 0 4 20mA 1 Select Excitation Voltage 12V 8V or 5V...

Page 12: ...i n deseada para este ciclo de trabajo de entrada Ciclo de trabajo de entrada Indicaci n deseada para este ciclo de trabajo de entrada 8 8 8 8 8 8 8 8 8 8 t Avr Pro Selecci n nivel de brillo de 1 a 4...

Page 13: ...elect inV reverse proportional variation if increasing frequency must result in a decreasing display In the duty configuration the meter is able to present a display proportional to the cyclic relatio...

Page 14: ...he value Configuration Lockout In mode RUN if the ENTER key is pressed for 3 seconds the meter will show the indication CodE and following 0000 allowing the user to introduce the security code If the...

Page 15: ...ot locked out giving access to all the programming levels Once completed the meter programming the following security measures are recommended 1 Lock out the programming access to prevent from program...

Page 16: ...g of the key TARE tArE Lock out menu diagram The following figure shows the lock out menu The access to this menu is accomplished from the run mode by pressing the ENTER key for 3 seconds until the Co...

Page 17: ...ut of parameters Menu partial lock out 0 unlocked 1 locked out Mode menu lock out SETPOINT1 menu lock out SETPOINT2 menu lock out SETPOINT1 value menu lock out SETPOINT2 value menu lock out Serial out...

Page 18: ...t activates when the display value exceeds the setpoint level and in LO mode the output activates when the display value falls below the setpoint PROGRAMMABLE TIME DELAY or HYSTERESIS Each output acti...

Page 19: ...o Hi Pro Setpoint 1 configuration block Delay Hysteresis selection Delay from 0 to 99s Hysteresis From 0000 to 9999 points of display Stor Set Activating mode selection Lo Low level activation Hi High...

Page 20: ...mA The output is opto isolated with respect to the signal input and the power supply The meter provides a two terminal connector and that drives out a signal variation from 0 20mA or 4 20mA proportio...

Page 21: ...t menu diagram 4 20 0 20 tyPE Hi Lo 8888 8888 Display para salida anal gica 0 4mA A out Display para salida anal gica 20mA Programaci n de la salida anal gica Pro Selecci n 0 20mA 4 20mA Analog output...

Page 22: ...9k NPN 1 5k PNP Logic level 0 2 4 VDC Logic level 1 2 6 VDC TTL 24V Encoder Input Logic level 0 2 4 VDC Logic level 1 2 6 VDC Switched Contact Input VC 5V internal RC 3 9k FC 20Hz Ton Toff 25ms Accur...

Page 23: ...maximum and minimum value refresh 10 times per second Relays 2 Relays Form A SPST normally open 5A 250VAC 30VDC Analog Output 0 4 20mA Resolution 5 5 A Accuracy 0 3 of reading 40 A EMI Max influence...