background image

12

Rev. (30-JAN-98) • RLM v4.7

© 1995-98 Automated Logic Corporation

Manually Formatting the Module

Manually formatting the module does not require
communication with the module.  Use this procedure as a
last resort when there is no communication with the
module.  Although down-loading memory overwrites all
existing memory, it requires communication in order to
initiate the transfer.

WARNING:  Formatting the module erases all
transferred memory.  The Transferring Memory
procedure must be followed after formatting.

1.

Turn the R683's power switch OFF.

2.

Set all eight of the R683's address and baud rate dip
switches to the ON position (see Figure 1 for
location).

3.

Turn the R683 module's power ON.

4.

Watch the LEDs on the R683 go through the
initialization process.

5.

Turn the R683's power switch OFF.

6.

Set the R683's address and baud rate using the 8-
position dip switch (see Figure 1 for location).

7.

Turn the R683 module's power ON.  The module is
now formatted.

LEDs

Identification

The R683's LEDs are identified as follows (see Figure 16
for location):

Digital Output Status- lights when output is activated.

Error - lights when a software error is detected.

Run - Blinks to indicate R683 is powered and executing
correctly.

Transmit - lights when the R683 transmits data to the
CMnet or access port.

Receive - lights when the R683 receives data through the
CMnet or access port.

LED Power-up Sequence

During power-up, the module goes through an
initialization and self test sequence.  Proper module
power-up may be verified by observing the LEDs as the
module is powered ON.

Shortly after power is applied to the module, the
following sequence occurs:

1.

The “Run” and “Error” LEDs will flash.

2.

Both LEDs will pause.

3.

The “Error” LED will turn off.

Figure 16:  R683 LEDs

Summary of Contents for R683

Page 1: ...ne Sensor 5 Enhanced Zone Sensor 5 Using the Enhanced Zone Sensor 6 Local Setpoint Adjust 6 Timed Local Override 6 Occupancy Indication 6 LocalAccess 7 UniversalInputs 9 Procedure 9 Custom Translation...

Page 2: ...s provided for diagnostic operations The R683 module can store a single Graphic Function Block GFB Specifications Power 24 VAC 50 60 Hz 20 VA 0 83 A maximum Inputs One enhanced zone sensor port and 8...

Page 3: ...he two large holes allow screws to pass through the module and hold the enclosure to the surface on which it is mounted see Figure 2 Panel Mounting To mount the R683 module directly to a surface the N...

Page 4: ...cation 6 Verify that 24 VAC is present at the power input NOTE Before turning the power on see Addressing and Baud Rate later in this document An error condition will occur if the address of the R683...

Page 5: ...nput 1 UI 1 connect the zone sensor wires to pins 1 and 2 on the 8 pin receptacle on the R683 module see Figure 5 3 Turn the module s power switch back ON 4 Input the channel number offset and gain on...

Page 6: ...page For example if the increment is set at 60 toggle the switch once for an occupancy of 60 minutes twice for 120 minutes etc Once the zone is occupied from this switch pressing it again and holding...

Page 7: ...ation is shown below The cable should not exceed 50 ft See Figure 11 for how to use the switches on the NI485 cable NOTE When making a sensor cable disregard the numbers imprinted on the plastic conne...

Page 8: ...8 Rev 30 JAN 98 RLM v4 7 1995 98 Automated Logic Corporation Figure 12 R683 I O Connections...

Page 9: ...pply see Figure 6 In some special cases when the module s power is limited a 4 20 mA passive transducer does require and external power supply to avoid power consumption from the module Table 1 Proced...

Page 10: ...r voltage to the desired units Procedure 1 Display the R683 module driver parameter page FB 15 in SuperVision 2 For thermistor slidepot and other resistance inputs set the option Is input specified in...

Page 11: ...dure 1 Turn the R683 s power switch OFF 2 Terminate the output wiring to the top termination strip as shown in Figure 12 3 Turn the R683 s power switch ON Digital Outputs The R683 has six digital outp...

Page 12: ...683 s power switch OFF 6 Set the R683 s address and baud rate using the 8 position dip switch see Figure 1 for location 7 Turn the R683 module s power ON The module is now formatted LEDs Identificatio...

Page 13: ...age and verify that the module type and number agrees with the module to be transferred 4 Transfer memory to this module For SuperVision 2 6 and earlier click on the Download icon and choose the Memor...

Page 14: ...5 06 Is input specified in voltage YES 0 Millivolts 0 00 500 Millivolts 50 00 1000 Millivolts 100 0 1500 Millivolts 150 0 2000 Millivolts 200 0 2500 Millivolts 250 0 3000 Millivolts 300 0 3500 Millivo...

Page 15: ...0 00 1 5 88 27 to 1 0 0 6 C 0 00 1 5 69 Zo ne Se nso r Inp ut RS Z Zo ne Se nso r Inp ut RS Z The rm isto r The rm isto r 39 39 1 7 to 2 13 F 0 00 1 5 88 27 to 1 0 0 6 C 0 00 1 5 69 S etpo int Ad jus...

Page 16: ...imer Normally at 10 minutes when the module is not halted Counts down when the module is halted or has other serious errors When it reaches zero the module re initializes itself to try to clear the so...

Reviews: