background image

11

Rev. (30-JAN-98) • RLM v4.7

© 1995-98 Automated Logic Corporation

7.

Transfer parameters to this FB.

8.

To activate these tables enter the gain of the
translation table used (either 15.00 or 15.06) on the
FB parameter pages that contain the input for which
the table applies.  Set the offset to 0.00.

NOTES:

1.

The minimum resistance for a setpoint adjust input
on the Enhance Zone Sensor port must be equal to
4.7k Ohms.  The minimum range for the slidepot on
the setpoint adjust input must be equal to 5k Ohms.

2.

The setpoint input bias parameter for slidepots is
only applicable if the slidepot is connected to the
setpoint adjust input (pin 3 on the Enhance Zone
Sensor, channel 3A.

3.

The setpoint input bias parameter for slidepots is
only applicable if the slidepot is connected to the
sepoint adjust input (pins 3 and 1 on the enhanced
sensor connection, channel 3A).

Analog Outputs

The R683 module has three analog outputs.  These
outputs may be used in the following modes:

Voltage Mode (0-10 VDC):

  1k Ohm minimum load

impedance.

Current Mode (4-20 mA):

  Although the R683's analog

outputs were designed to output voltage, it is possible to
use these outputs for current mode devices. To do this,
wire a 1/2 Watt resistor in series with the resistive load,
(as shown in Figure 12).  The value of the series resistor is
determined as follows:

R

SERIES

 = 500 Ohms - R

LOAD

Example: To drive a 100 Ohm resistive load with a
0-20 mA signal, subtract the load resistance from 500
Ohms:

R

SERIES

 = 500 Ohms - R

LOAD

= 500 Ohms - 100 Ohms

= 400 Ohms

This example is shown in Figure 12.

Procedure

1.

Turn the R683's power switch OFF.

2.

Terminate the output wiring to the top termination
strip as shown in Figure 12.

3.

Turn the R683's power switch ON.

Digital Outputs

The R683 has six digital outputs which can be connected
to a maximum of  24 Volts AC/DC (see Figures 12).  The
digital outputs can be configured as dry contact
(normally open) with a contact rating of 3 A (maximum).

Procedure

1.

Turn the R683's power switch OFF.

2.

Terminate the output wiring to the top termination
strip as shown in Figures 12.

NOTE:  Pilot relays should not be powered from the
same transformer which powers the R683.

3.

Turn the R683's power switch ON.

By setting the HOA switches (see Figure 1), each digital
output can be placed in ON, OFF, or AUTO mode.  The
position of the HOA switches may be monitored through
channels 81-86.  Channel 81 corresponds to channel 11,
channel 82 to channel 12, etc.  A status of OFF on these
channels indicates the switch is set to AUTO mode.  A
status of ON indicates the switch is set to either ON or
OFF mode.

Checkout & Troubleshooting

Checkout is performed using either the Workstation or a
portable computer that is direct-network connected to the
module.  To use a portable computer, connect an NI485N
cable to the “ACCESS” connector, located in the lower
right corner of the module (see Figure 10).

NOTE:  Do NOT separate the NI485N cable adapter with
the LED on it from the rest of the cable.  This adapter
contains circuitry essential for proper communication.

Check each input by manually causing each sensor to
establish a known condition and then comparing it to the
condition reported on the FB's status page.

Check each output by locking it to a known condition on
the FB's parameter page and then observing that
equipment's operation.

Summary of Contents for R683

Page 1: ...ne Sensor 5 Enhanced Zone Sensor 5 Using the Enhanced Zone Sensor 6 Local Setpoint Adjust 6 Timed Local Override 6 Occupancy Indication 6 LocalAccess 7 UniversalInputs 9 Procedure 9 Custom Translation...

Page 2: ...s provided for diagnostic operations The R683 module can store a single Graphic Function Block GFB Specifications Power 24 VAC 50 60 Hz 20 VA 0 83 A maximum Inputs One enhanced zone sensor port and 8...

Page 3: ...he two large holes allow screws to pass through the module and hold the enclosure to the surface on which it is mounted see Figure 2 Panel Mounting To mount the R683 module directly to a surface the N...

Page 4: ...cation 6 Verify that 24 VAC is present at the power input NOTE Before turning the power on see Addressing and Baud Rate later in this document An error condition will occur if the address of the R683...

Page 5: ...nput 1 UI 1 connect the zone sensor wires to pins 1 and 2 on the 8 pin receptacle on the R683 module see Figure 5 3 Turn the module s power switch back ON 4 Input the channel number offset and gain on...

Page 6: ...page For example if the increment is set at 60 toggle the switch once for an occupancy of 60 minutes twice for 120 minutes etc Once the zone is occupied from this switch pressing it again and holding...

Page 7: ...ation is shown below The cable should not exceed 50 ft See Figure 11 for how to use the switches on the NI485 cable NOTE When making a sensor cable disregard the numbers imprinted on the plastic conne...

Page 8: ...8 Rev 30 JAN 98 RLM v4 7 1995 98 Automated Logic Corporation Figure 12 R683 I O Connections...

Page 9: ...pply see Figure 6 In some special cases when the module s power is limited a 4 20 mA passive transducer does require and external power supply to avoid power consumption from the module Table 1 Proced...

Page 10: ...r voltage to the desired units Procedure 1 Display the R683 module driver parameter page FB 15 in SuperVision 2 For thermistor slidepot and other resistance inputs set the option Is input specified in...

Page 11: ...dure 1 Turn the R683 s power switch OFF 2 Terminate the output wiring to the top termination strip as shown in Figure 12 3 Turn the R683 s power switch ON Digital Outputs The R683 has six digital outp...

Page 12: ...683 s power switch OFF 6 Set the R683 s address and baud rate using the 8 position dip switch see Figure 1 for location 7 Turn the R683 module s power ON The module is now formatted LEDs Identificatio...

Page 13: ...age and verify that the module type and number agrees with the module to be transferred 4 Transfer memory to this module For SuperVision 2 6 and earlier click on the Download icon and choose the Memor...

Page 14: ...5 06 Is input specified in voltage YES 0 Millivolts 0 00 500 Millivolts 50 00 1000 Millivolts 100 0 1500 Millivolts 150 0 2000 Millivolts 200 0 2500 Millivolts 250 0 3000 Millivolts 300 0 3500 Millivo...

Page 15: ...0 00 1 5 88 27 to 1 0 0 6 C 0 00 1 5 69 Zo ne Se nso r Inp ut RS Z Zo ne Se nso r Inp ut RS Z The rm isto r The rm isto r 39 39 1 7 to 2 13 F 0 00 1 5 88 27 to 1 0 0 6 C 0 00 1 5 69 S etpo int Ad jus...

Page 16: ...imer Normally at 10 minutes when the module is not halted Counts down when the module is halted or has other serious errors When it reaches zero the module re initializes itself to try to clear the so...

Reviews: