background image

 

 

CHARGING STATION

 

«WALL COMPLEX»

 

 

User manual

Summary of Contents for WALL COMPLEX

Page 1: ...CHARGING STATION WALL COMPLEX User manual ...

Page 2: ...efully compiled at the time of publication Under no circumstances will compliance with the information in this Manual relieve the user of his responsibility to comply with all applicable codes safety standards or wiring regulation The developer cannot be held liable for any direct or indirect damages resulting from the use or operation of the electrical circuits of the equipment or software descri...

Page 3: ...CATIONS 10 2 PACKAGE 11 3 MARKING 12 4 INSTALLATION 12 4 1 OPERATING LIMITATIONS 12 4 2 COMPLEX INSTALLATION 13 4 3 STATION CONNECTING 16 5 OPERATION 18 5 1 OPERATING MODES AND ELECTRIC VEHICLE CHARGING PROCESS 18 5 2 CONNECTING THE VEHICLE 19 5 3 SAFETY MEASURE 20 6 MAINTENANCE 20 7 TROUBLESHOOTING 22 8 STORAGE 22 9 TRANSPORTATION 23 10 DISPOSAL 23 11 FAT CERTIFICATE 23 11 1 ADDRESS OF MANUFACTUR...

Page 4: ...nel and fully understood Important safety instructions in this manual are indicated by symbols These safety instructions must be strictly followed You should always pay attention to them and follow the safety requirements to avoid accidents personal injury or property damage WARNING Risk of injury or death This symbol indicates instructions that must be followed to avoid injury trauma or death ATT...

Page 5: ...tware described in this manual The manufacturer is not responsible for damage and or malfunctions caused by non compliance with the instructions in this manual The manufacturer will not be liable for any personal injury or material damage whether indirect or special consequential loss of business profits business interruption or loss of business information resulting from the use of the equipment ...

Page 6: ...rol system that handles communication between the station and the electric vehicle The control and protection functions operate continuously in the system The station is available in several modifications All modifications are equipped with from one to five fixed cables with Type 1 Type 2 CHAdeMO CCS Type 1 CCS Type 2 GB T AC GB T DC connectors in various combinations 1 2 FUNCTIONAL POSSIBILITIES ...

Page 7: ...Smartphone app Chip tag extra option Mechanical protection IK10 Case protection class IP54 Operating temperature от 35 C до 50 C Relative humidity no more than 95 without moisture condensation Mass kg 240 Charging station dimensions H W D mm 1065 1063 311 Dimensions with pedestal H W D mm 2126 1063 630 Communication and protocols 2G GSM GPRS Class 12 Quad band 850 900 1800 1900MГц 3G 4G LTE LTE Ca...

Page 8: ...t 40 A 80 A Maximum socket voltage 230 V Cable length 6 5 m Charging connector Type 2 Mennekes Maximum power per socket 22 kW 43 kW Maximum current per socket 3 32 A 3 63 A Maximum socket voltage 400 V Cable length 6 5 m Charging connector CHAdeMO Maximum power per socket 100 kW Maximum current per socket 200 A Maximum socket voltage 500 V Cable length 5 5 m ...

Page 9: ...r per socket 100 kW 300 kW Maximum current per socket 200 A 300 A Maximum socket voltage 500 V 1000 V Cable length 5 5 m Charging connector GB T AC Maximum power per socket 22 kW 43 kW Maximum current per socket 3 32 A 3 63 A Maximum socket voltage 400 V Cable length 6 5 m Charging connector GB T DC Maximum power per socket 100 kW 187 5 kW Maximum current per socket 200 A 250 A Maximum socket volt...

Page 10: ...4 121 1xType1 18 4 kW 48 4 70 4 92 4 91 4 134 4 78 4 100 4 123 122 165 2xType1 36 8 kW 66 8 88 8 109 8 96 8 118 8 139 8 PType1 PType2 No Type2 1xType2 22 kW 2xType2 44 kW 1xType2 43 kW 2xType2 86 kW Type2 отсутствует 1xType2 22 kW 2xType2 44 kW 1xType2 43 kW 2xType2 86 kW PDC PType1 PDC 90 kW PDC 120 kW No Type1 90 112 134 133 176 120 142 164 163 206 1xType1 9 2 kW 99 2 121 2 143 2 142 2 185 2 129...

Page 11: ...od Wall mounting EV charging station Wall Complex 1 User manual 1 Mounting bracket 1 Anchor screw M8 4 Pedestal mounting EV charging station Wall Complex with pedestal 1 User manual 1 Inserts 1 Nut M16 4 Washer 16 4 Additional accessories Cable pull up unit tensioner 2 Figure 1а Station external view and station dimensions for wall mounting ...

Page 12: ... the model serial number and basic technical specifications 4 INSTALLATION 4 1 OPERATING LIMITATIONS The charging station is designed exclusively for charging electric vehicles Charging only compatible electric vehicles Failure to comply with the requirements for operation maintenance and repair described in this manual excludes any liability of the manufacturer in the event of malfunctions in the...

Page 13: ... there must be a distance of at least 1 meter to the left and right of the station body to any obstacle The holes for the anchor screws should be positioned as shown in Figure 2 For pedestal mounted charging stations prepare the installation site in advance by following the instructions below Figure 2 Mounting bracket When choosing a location for the charging complex the following conditions must ...

Page 14: ...destal base are shown in Figure 4 the plate thickness is 8 mm Along with the preparation of the foundation it is necessary to ensure the laying of an electric power cable not included in the delivery set The required cable length above the foundation is at least 2 5 meters Figure 4 Pedestal base bottom view ...

Page 15: ...with a cross section of 5 50 mm2 to 5 95 mm2 Table 2 Recommended cross section of power cable Charging station power kW Cross section of power cable mm2 75 5 16 75 98 5 25 98 118 5 35 118 148 5 50 148 181 5 70 181 225 5 95 It is necessary to install an AC circuit breaker between the station and the power supply network when the power cable laying It is recommended to use a 3 pole circuit breaker i...

Page 16: ...tive grounding with a separate wire To connect the complex to the electric circuit it is necessary to open the cover of the charging station and lead the power cable through the cable entry channel to the internal part of the station ATTENTION A combination lock is used The default lock code is 000 On the underside outer edge of the lock there is hole for the code reset button Rotate the face of c...

Page 17: ... result in energizing the charger body electric shock damage to the service personnel and consumers as well as in a failure of the charger Then with the help of external switching devices it is necessary to connect the power cable to the AC mains and then move the three pole circuit breakers to the working position To switch the charging complex on it is necessary to Install mobile operator s SIM ...

Page 18: ... modem number station number in Autoenterprise billing mobile network status etc The information shown on the display depends on the software version and may differ from version to version After the supply voltage is applied the station display shows information about the software version and the serial number of the modem In case of malfunctions in the operation of the charging complex you must i...

Page 19: ...LL COMPLEX 19 The DC Output indicator flashes green quickly when the car is charging in DC Mode CHAdeMO CCS GB T DC In this case the LCD display shows information about charging parameters 5 2 CONNECTING THE VEHICLE ...

Page 20: ...s an emergency shutdown button in the DC charging mode When the emergency stop button is pressed in DC charging mode the electrical circuit that powers the vehicle s battery is automatically disconnected The message EMO PRESSED appears on the display To continue the operation of the complex the emergency stop button must be manually returned to its original state turn the button counterclockwise 6...

Page 21: ...harging complex is operating in conditions of increased dustiness it is recommended to carry out extraordinary routine maintenance for preventive cleaning of the internal elements of the complex from dust at least once every 3 months Preventive inspection of the charger should be carried out at least once every 3 months To do this the charger must be disconnected from live circuits and its housing...

Page 22: ...k of voltage Restore power supply Circuit breaker s tripped off Bring circuit breaker s to operating position Display is out of order Contact to Customer Service Other malfunction Malfunctions caused by external and internal factors Contact to Customer Service CUSTOMER SERVICE You can write an email or call to the tech support using the contact page on our web site autoenterprise ua 8 STORAGE The ...

Page 23: ...perature range 0 C to 40 C 32 F to 104 F 10 DISPOSAL ATTENTION The symbol with the crossed out waste container means that electrical and electronic devices including their accessories must not be disposed in the household garbage Please observe the regulations regarding disposal of electric appliances and electronic devices Electronic components of the charging station must be disposed in accordan...

Page 24: ... that was damaged in normal use at no charge to Owner for material and or labour Owner pays any transportation costs associated with the replacement repair of components to the manufacturer factory or any other repair location indicated by manufacturer If the repair issue cannot be resolved remotely Owner shall at its own expense ship the Product s to a Repair Centre after receipt of respective in...

Page 25: ...ther equipment in the possession of the consumer as a result of malfunctions or defects arising during the Warranty period Furthermore damage to the electrical vehicle itself is never covered by this Warranty Manufacturer or its authorized distributors will not be liable for any indirect incidental special punitive or consequential damages even if manufacturer knew or should have known of the poss...

Reviews: