Wiring instructions

WARNING: 

Make sure that all power is disconnected before starting the installation.

1.

At the electrical box, connect the building wiring to the CKT + and CKT - terminals on the assembly.

2.

To ensure proper continuity, use a torque wrench to tighten the terminal block screws to 12-15 inch-pounds.

3.

Maintain the correct polarity for each strobe unit.

Note: 

Signal Line Circuit (SLC) wiring must be twisted pair (TWP). CKT Terminals accept 2 Wires: 12-18 AWG TWP.

WARNING: 

Do not bring the conduit through the rear of the electrical box. Strip the lead insulation to 7/16 inches maximum.

Figure 2: Wiring instructions

Wiring notes:

a.

The maximum number of addresses on an IDNAC channel is 127. The maximum number of active appliances is limited to 3 amps per

circuit. Refer to the field wiring diagrams for the driving compatible fire alarm control panel for further instructions.

b. Notification appliances are rated using an individual module label.

c.

Maintain the correct polarity on the terminal connections.

d. Ter and - can each accommodate 2 wires, one wire going in and one wire going out to the next appliance.

e.

These appliances are rated to the operating voltage limits of 23-29.5 VDC. The appliance may fail to operate as intended, and may cause

permanent damage to this equipment if it operates outside of these limits.

f.

Use a compatible IDNAC power supply to operate the TrueAlert ES AO appliance.

g.

T-tapping is not permitted on Class A wiring.

h. TrueAlert SLC wiring connections are supervised and power-limited.

i.

Compatible IDNAC power supplies/panels: 4100ES, EPS, ES Power Supply, IDNAC card, 4007ES, 4010ES, and 4009 IDNAC Repeater.

page 2

579-1200AC  Rev. E

TrueAlert ES Addressable Indoor Audible Notification Appliance installation instructions

Summary of Contents for TrueAlert ES A59AOC-WRF

Page 1: ...c requirements of the local Authority Having Jurisdiction AHJ These notification appliances are not intended for installation within hazardous locations as defined by the National Electrical Code NEC or NFPA UL listed TrueAlert ES indoor product identification reference Table 1 Product identification reference Type Colors Models Wall Mount Audible Only A O Red White Components A59AO APPLWR A59AO A...

Page 2: ...he field wiring diagrams for the driving compatible fire alarm control panel for further instructions b Notification appliances are rated using an individual module label c Maintain the correct polarity on the terminal connections d Terminals and can each accommodate 2 wires one wire going in and one wire going out to the next appliance e These appliances are rated to the operating voltage limits ...

Page 3: ...e appliance at this address with the Fire Alarm Control Panel FACP system configuration documentation DIP switch position 8 determines whether this appliance is viewed by the system as an ALARM OFF or ALERT ON type appliance Figure 3 Setting the DIP switch address Setting the appliance configuration You can configure certain options for the horn and strobe directly on the appliance using the appli...

Page 4: ...lume settings are configured with DIP Switch CFIG1 See Figure 4 4 If you install the A4905 9838 Sound Damper the anechoic measurements decrease by approximately 9 dBA Table 4 ULC directional characteristics for horn Axis Angle dBA 50 left and right 3dBA Horizontal 63 left and right 6dBA 20 above 48 below 3dBA Vertical 65 above 60 below 6dBA CAUTION The appliances are available in red and white Do ...

Reviews: