Autocall A49SVH-APPLC-O Installation Instructions Manual Download Page 1

579-1241AC Rev A

TrueAlert ES Addressable US/Weather Proof Ceiling Mount Speaker Notification Appliances

Installation Instructions

*05791241ACA*

Cautions, warnings, and regulatory information

Important: 

When the notification appliance emits light or sound, it indicates the possibility of an emergency situation that requires immediate atten-

tion of all occupants.

SAFETY:

 Always install, maintain, and test notification appliances within their specifications. Failure to follow all safety precautions and

instructions may result in loss of life and property due to non-functioning notification appliances. Some notification appliances use high

voltage. To avoid electrical hazards and avoid damage to appliances, make sure that the electrical power for the Notification Appliance

Circuit is disconnected at the control panel before installing, repairing, or internally adjusting any notification appliances. Even with

electrical power removed, some notification appliances (such as visible strobes) store a high voltage charge. The high voltage can cause

injury resulting in death from electrical shock. DO NOT TOUCH EXPOSED CIRCUITRY.

LOCATION REFERENCE:

 Location and quantity of appliances required must conform to the applicable local standards and guidelines

(the National Fire Alarm and Signaling Code (NFPA 72); ULC Standard CAN/ULC-S524, Installation of Fire Alarm Systems; the appropriate

model building codes, etc.) and specific requirements of the Local Authority Having Jurisdiction (AHJ). These notification appliances are

not intended for installation within hazardous locations as defined by the National Electrical Code (NEC) or NFPA.

UL listed TrueAlert ES indoor product identification reference

Table 1: Product Identification Reference

Type

Cover

colors

Models

Operation

Figure 1: Ceiling

Mount

Speaker/

Visible(S/V)

with cover

• Red
• White

Components:

A49SVH-APPLC-O
A49SVH-APPLC-O

Covers:

A49SVC-CRALT-O
A49SVC-CRFIRE-O
A49SVC-CRS-O
A49SVC-CRBC-O
A49SVC-CWBC-O
A49SVC-CWFIRE-O
A49SVC-CRFEU-O

A49SVC-CRBF-O

A49SVC-CWALT-O
A49SVC-CWBA-O
A49SVC-CRBA-O
A49SVC-CWS-O
A49SVC-CWBF-O
A49SVC-CWFEU-O
A49SVC-CK-O

Back boxes:

A49WPBB-SVCR
A49WPBB-SVCW

Figure 2: Ceiling

MountS

peaker

Only (SO)

with cover

• Red
• White

Components:

A49SO-APPLC-O
A49SO-APPLC-O-BA

Covers:

A49SOC-CW-O
A49SOC-CR-O
A49SOC-CWALT-O
A49SOC-CRALT-O
A49SOC-CRFIRE-O

A49SOC-CRS-O
A49SOC-CWFIRE-O
A49SOC-CWS-O
A49SOC-CK-O

Back boxes:

A49WPBB-SOCR
A49WPBB-SOCW

These appliances provide an

audible (SO) or audible/visible (S/

V) warning of an alarm condition

when activated from the control

panel of a compatible UL/ULC

Listed, Autocall Fire Alarm

System. Consult Autocall Fire

Alarm panel documentation for

compatibility information. The

speakers can be turned ON/OFF

individually under compatible

panel control.

Kit contents:

Appliance x1, with 1.25 inch thread forming screws (#8-16 thread) x 4.

Not included:

Order a back box to mount the appliance assembly to the ceiling. Order a cover separately for each appliance.

Note: 

For information about TrueAlert ES appliance testing consult 

TrueAlert ES Addressable Appliances Troubleshooting 

(579-1049AC).

Strobe operation levels

The A49 S/V appliances have multiple strobe intensity levels. Levels W135, W110, and W185 are rated for UL outdoor private mode applications. Level

110 is rated for UL indoor and uncontrolled wet Public Mode applications.

Summary of Contents for A49SVH-APPLC-O

Page 1: ...locations as defined by the National Electrical Code NEC or NFPA UL listed TrueAlert ES indoor product identification reference Table 1 Product Identification Reference Type Cover colors Models Operation Figure 1 Ceiling Mount Speaker Visible S V with cover Red White Components A49SVH APPLC O A49SVH APPLC O Covers A49SVC CRALT O A49SVC CRFIRE O A49SVC CRS O A49SVC CRBC O A49SVC CWBC O A49SVC CWFIR...

Page 2: ...or the A49SVH align the cover mounting tab with the strobe dome and carefully place the cover over the unit 6 Press the cover until it snaps into place Cover SO Appliance Weather proof back box Cover S V Appliance Weather proof back box Screws 8 16 x 1 25 inch Screws 8 16 x 1 25 inch Figure 3 Mounting instructions Wiring instructions Warning Make sure that all power is disconnected before starting...

Page 3: ...an individual module label 3 Maintain the correct polarity on the terminal connections 4 Terminals 1 through 6 each accommodate two wires one wire going in and one wire going out to the next appliance 5 These appliances are rated to the operating voltage limits of 23 30 VDC The appliance can fail to operate as intended and can cause permanent damage to this equipment if it operates outside of thes...

Page 4: ...address Setting the strobe candela setting 1 The jumpers are factory set to FACP Use this setting when programming the candela setting at the 4100ES FACP The candela setting is visible through the slot on the side of the appliance 2 For manual selection remove the cover and slide the candela flag to the required setting W75 W110 W185 110 candela or FACP The candela setting is visible through the s...

Page 5: ...erature rating for indoor and uncontrolled wet Public Mode 110 CD 0 F to 120 F 0 C to 49 C FM temperature rating 40 F to 120 F 40 C to 50 C UL ULC humidity range 95 non condensing at 60 F 60 C Connections Terminal for 18 AWG to 12 AWG 0 82 mm 2 to 3 31 mm 2 CAUTION The appliance covers and backboxes are available in red and white Do not paint or otherwise alter the factory finishes in any way Tabl...

Page 6: ...0 103 60 40 111 65 35 98 65 35 120 70 35 87 70 35 103 75 30 90 75 30 75 80 30 96 80 30 83 85 25 96 85 25 70 90 25 83 90 25 47 Table 6 TrueAlert Addressable Ceiling Mount S V and SO Units speaker switch setting and output ratings 25 V or 70 V audio Tap Settings in Watts UL reverberant at 10 ft ULC anechoic at 3 m 1 4 80 82 1 2 83 85 1 86 88 25 V 2 88 90 1 4 78 80 1 2 82 84 1 85 87 70 7 V 2 88 90 No...

Reviews: