![Autocall 4007ES Operator'S Manual Download Page 11](http://html.mh-extra.com/html/autocall/4007es/4007es_operators-manual_3021010011.webp)
Page 9
579-1165AC Rev C
4007ES Operator’s Manual
4.2.6 Reset the System
Resetting the system allows it to return to a normal state after alarm activation.
IMPORTANT:
Reset the system only after the source of the alarm is determined and dealt with.
1.
Tap the
Alarm Functions
button.
Date
Time
Fire Alarm in System
PULL STATION 1
FIRE ALARM
Date
First of 1
Menu
Alarm Functions
ACK
1
Fig 10: Alarm functions button
2.
Tap the
System Reset
button.
Fire Alarm in System
System Reset
USER
BUTTON 1
USER
BUTTON 2
USER
BUTTON 3
Alarm Silence
100%
Fig 11: System reset
3.
Confirm the selection.
Fig 12: Confirm
Note:
1.
If a zone or device has reset successfully, the user interface returns to its normal display.
2.
If a zone or device remains in alarm when you reset the system, the system reset aborts. A message confirming the abort displays on the
user interface.