Alarm text
Comment
Overspeed
Engine running faster than the overspeed setpoint.
Engine Stopped
Engine stopped for no known reason.
Engine failed to stop
60 seconds after issuing the stop command, the engine has
still not stopped.
Start Failure
Engine failed to start after the last start attempt.
Pickup failure
Unable to read the pickup signal while engine is running.
Output circuit overload
Short circuit in one of the +24V outputs.
The outputs are secured with fuse F3 that makes an
automatic reset. Remove the overload to correct the
problem.
For details, see page 21.
Analogue sensor failure
[A7]
Detailed information on which analogue channel that is
below 2mA. Here channel 7.
Broken wire [T7 T9 T44]
Information on which terminal has a broken wire. Here on
terminal 7, 9 and 44.
Adjusting the LCD screen
The control unit uses a graphical Liquid Crystal Display.
The optical performance of the display changes with temperature,
light conditions and age.
There is a built-in automatic compensation for temperature changes.
Still, from time to time, it may be necessary to adjust the display.
Automatic Backlight Shutoff
To preserve LCD lifetime, the display automatically shuts off after
the predefined amount of time, if no action has been observed in that
period.
The display turns on again at any key press, or if an event occurs in
the system.
Note:
The terminals 61 and 62 can be configured as LCD Backlight
On. A 0V on the terminal will trigger the LCD Backlight On.
Contrast
Contrast is automatically compensated for with temperature.
If however the display seems dim or unclear, it may be necessary to
adjust it. Access the menu and select Contrast to adjust.
The new setting is automatically stored in internal memory, and stays
resident regardless of future power loss.