Time behaviour and particularities

+

NOTE

Acquiring data with PLC-ANALYZER pro results in a small increase in cycle time in the
PLC to the same manner as it happens with programming software PSS WIN-PRO in
the online-mode.

The intervals between scan transfers from the PILZ PLC to the computer are depending on the following
items:

CPU type

cycle time of PLC

Number of recorded addresses.

For the PSS SB 3006-3 ETH-2 the scan interval for a address is approximately 5 ms, i.e. for a cycle time > 5
ms there is one scan for each cycle. For a longer PLC cycle time data transfer is synchronized with the PLC
cycle. For a shorter cycle time the computer does not obtain a scan for each cycle, resulting in a partial
loss of information. This loss can be compensated by repeated measurements of the interesting signals.

Every additional requested address leads to an increase in scan time of about 0.1 ms. The following
table exemplarily shows some values of time behaviour during acquisition:

Requested data

Scan time

1 flag byte

5 ms

50 flag words

11 ms

100 flag words

22 ms

1 flag byte, 1 output byte

5 ms

50 flag byte, 50 data words

23 ms

10 flag words, 10 data words, 10 inputs, 10 outputs

10 ms

Table 1-2 Scan times on PSS SB 3006-3 ETH-2

The following table shows typical scan times for PILZ PSS 3046 (cycle time ca. 40ms):

Scandata

Scan time

1 Byte

90 ms

32 Words 

120 ms

Table 1-3 Recording time PILZ PSS 3046

Summary of Contents for PLC-ANALYZER pro 6

Page 1: ......

Page 2: ...M GmbH Dithmarscher Straße 29 26723 Emden Germany 49 4921 9610 0 info autem de www autem de AUTEM does not give any warranty for this manual as well as no express or tacit warranties on commercial quality and suitability for a particular use AUTEM does not take over adhesion for errors contained in it or for damages that may occur as a result of using or applying this material The soft and hardwar...

Page 3: ...urce 3 PILZ PSS PNOZ 3 Installation 3 Installing additional hardware 3 Installing additional software 3 Configuration 4 Data acquistion 6 Supported PLC models and CPUs 6 Recordable PLC addresses 6 Number of recordable addresses 6 Time behaviour and particularities 7 ...

Page 4: ...may occur in the automated facility endangering humans or causing large scale material damage must be prevented by additional precautions These precautions e g independent limit monitors mechanical interlocks must guarantee safe operation even in case of dangerous errors Installation The PLC driver can be added to the project as a new signal source If the driver you want is not yet in the list of ...

Page 5: ...settings to set important parameters for data recording If you have added the driver to the project several times you can set the properties individually for each individual driver Fig 1 1 Settings PILZ PSS Ethernet TCP IP Fig 1 2 Settings PILZ PSS Ethernet TCP IP ...

Page 6: ...l at which measured values are read out from the PLC A longer sampling interval can be selected for signal paths that are not time critical e g temperature As a result the generated signal files become smaller Under Symbols select a Symbol file to make the symbols available for address selection This makes it possible to use symbolc identifiers when entering addresses In addition to the absolute a...

Page 7: ...E 17 23 EB y z PSS input byte y z EB 23 24 EW x z PSS input word x z EW 14 16 O y z PNOZ output byte y bit z O 32 4 OB y z PNOZ output byte y OB 9 24 OW x z PNOZ output word x z OW 14 00 I y z PNOZ input byte y bit z I 17 23 IB y z PNOZ input byte y z IB 23 24 IW x z PNOZ input word x z IW 14 16 M y z Flag byte y bit z M 3 07 MB y z Flag byte y z MB 25 08 MW x z Flag word x z MW 24 16 T x Status T...

Page 8: ...ronized with the PLC cycle For a shorter cycle time the computer does not obtain a scan for each cycle resulting in a partial loss of information This loss can be compensated by repeated measurements of the interesting signals Every additional requested address leads to an increase in scan time of about 0 1 ms The following table exemplarily shows some values of time behaviour during acquisition R...

Reviews: