Aurora AU-EMLD2 Instructions Download Page 1

                                        

  

 

Aurora Limited    16 Alban Park    Hatfield Road    St Albans    Hertfordshire    AL4 0JJ   United Kingdom 

Website: www.auroralighting.com  

Document version – AU-EMLD2_3_V2_14 - ENG&FRE

 

 

AU-EMLD2 & AU-EMLD3 – NON-MAINTAINED LED EMERGENCY PACK 

 

PLEASE READ THESE INSTRUCTIONS CAREFULLY BEFORE INSTALLATION 

LEAVE A COPY FOR THE USER / MAINTENANCE ENGINEER FOR FUTURE REFERENCE 

IMPORTANT INSTALLATION INFORMATION

 

 

Installation should be carried out in accordance with the latest edition of the National Wiring Regulations. If in doubt please consult a qualified electrician. 

 

This unit requires an unswitched 230-240V mains supply to charge the battery. 

 

This is a Non-maintained unit and will only energise in the event of an electrical mains supply failure. 

 

Ensure that ALL connections are tight with no loose strands, including factory connections. 

 

Batteries must be charged for 24 hours to ensure full emergency duration and before testing. 

 

A green LED within the module indicates the battery is charging correctly. 

 

LED module may also be mounted without the downlight in a 20mm hole. 

 

Please note - There is basic insulation between the battery and supply. 

 

Battery discharge rated current: 0.55A 

 

The bve and -ve connections must be correct. If reversed the product will not operate. 

 

INSTALLATION INSTRUCTIONS 

Isolate the mains supply before servicing or installation

 

1.

 

Select the required position for the luminaire. Beware of joists, water pipes and electric cables. 

2.

 

Drill the cutout in the position required (Cutout is 40mm diameter). 

3.

 

Connect the pack to the mains supply, Brown to the Live supply (Red or Brown) and Blue to the Neutral (Black or Blue) using a suitable junction box. 

4.

 

Connect the battery to the driver using the AMP connector 

5.

 

Push the emergency train through the cutout in the ceiling. 

6.

 

Slide the legs of the mounting spring clips into the ceiling cutout and push the fitting up into the aperture. 

FIG. 1 

 

 

Environmental Protection (W.E.E.E.) – Aurora’s WEEE Reg.No. WEE/BG0130YX (UK Only)

 

 

Waste Electrical & Electronic Equipment Regulations (WEEE) requires that any of our products showing this marking (left) must not be disposed of with other 
household or commercial waste. Aurora does not levy any WEEE disposal charges to its customers for affected WEEE related products. To prevent possible harm 
to the environment or human health from uncontrolled waste disposal, please separate any such product from other waste types and recycle it responsibly at your 
local facilities. Check with your Local Authority, Recycling Centre or retailer for recycling advice. If, when you purchased any Aurora product, your supplier 
included a WEEE disposal fee, you should then contact your supplier for advice on his take back of the product for the correct disposal. 

WARRANTY 

See www.auroralighting.com/warranty for full details of warranties and Extended Warranty Terms and Conditions. The warranty is invalid in the case of improper use, tampering, 

and removal of the Q.C. date label, installation in an improper working environment or installation not according to the current edition of the National Wiring Regulations. Should 

this product fail during the warranty period it will be replaced free of charge, this is subject to correct installation and return of the faulty product. Aurora does not accept 

responsibility for any installation costs associated with the replacement of this product. This warranty is in addition to the statutory rights in your country of purchase. Aurora 

reserves the right to alter specifications without prior notice. 

 