Assembly Instruction
KSA - T

WIN

 S12 24V DC

T

ARGET

 G

ROUP

These instructions are intended for qualifi ed operators of Natural Smoke 
and Heat Exhaust Ventilation systems (NSHEV /SHEV) and Natural Venti-
lation of windows and familiar with the operating modes as well as with 
the residual risks of the system.
This  device  is  not  intended  to  be  used  by  persons  (including  children) 
with limited physical, sensory or mental aptitude or lack of experience 
and/or knowledge unless they are supervised by a person responsible for 
their safety or have received instruction from this person as to how the 
device is used. Children should be supervised to ensure that they do no 
play with the device.
Cleaning and user servicing must not be carried out by children without 
being supervised.

Operation of the power-operated window

Switchs  with  OFF-default  setting  (i.  e.  key  switch)  shall  be
located  within  eyeshot  of  the  operated  window  but  in  a  safe  dis-
tance  from  moving  parts.  If  it  is  not  a  key  switch,  the  switch  must 
be  installed  at  a  height  of  at  least  1.5  m  and  out  of  reach  for  un-
authorized operation.

Drives

 that are provided with a manual actuator must be provided with 

a sign indicating how to use it. The sign shall be fi xed permanently and 
clearly visible next to the manual actuator.

 

During the opening operation all persons should

 

be  kept  clear  off  the  window  -  directly  below 

 

or right next to it (within the opening radius of

 

the casement) since operating the manual switch

 

may  lead  to  uncontrolled  movements  of 

 

the driven part, for example due to mechanical 

 

failure or imbalance.

Do not allow children playing with fi xed control devices and keep remote 
controllers out of children’s reach.

Keep all other persons clear off the window if a switch with OFF-default 
setting is operated when the window closes. Keep all other persons clear 
off  the  window  that  closes  when  being  operated  by  a  smoke  exhaust 
system.

 

Do  not  operate  the  window  during  repair  or

 

adjustment work.

W

ARRANTY

 

AND

 

AFTER

-

SALES

 

SERVICE

Basically our: 

„General Terms and Conditions of Goods and Services by the Elec-
trical Industry” issued by the Central Association of the Electrical 
Engineering and Electronics Industry (ZVEI) are applicable.

This  warranty  complies  with  legal  requirements  and  applies  to  the 
country in which the drive was purchased.
The warranty covers material and manufacturing faults that occur during 
normal use of the products.

The warranty period for materials supplied is 12 months.

Warranty and liability claims with damages to property and persons will 
be excluded if they are due to one or several of the following causes:

•  Improper use of the drive.

•  Improper assembly, commissioning, operation, maintenance or repair 
  of the drive.

•  Operating the drive with defective, improperly installed or malfunc-
  tioning safety and protection devices.

•  Failure to comply with the notes and assembly pre-requisites as speci-
  fi ed in these instructions.

•  Unauthorized  constructional  modifi cations  to  the  drive  or  to  ac-
  cessories.

•  Cases of catastrophe caused by foreign objects and Acts of God.

•  Wear.

For possible warranty claims or required spare parts or accessories please 
contact your nearest branch offi ce or the competent contact person at 

 Aumüller Aumatic GmbH.

Details can be found on our website

(

www.aumueller-gmbh.de

). 

L

IABILITY

We reserve the right to change or adjust products at any time without 
prior notice. Illustrations are subject to change. Although we take every 
care to ensure accuracy, we cannot accept liability for the content of this 
document.

R

EMOVAL

 

AND

 

DISPOSAL

To remove the drive, reverse the sequence used for fi tting. Adjustment 
work is not required.

1.   Before removing a drive, disconnect it from the power supply.
2.   When  removing  a  drive,  the  window  must  be  secured  against
 

unintended opening.

Dispose of the parts in accordance with the applicable local or national 
legal regulations.

!

C

AUTION

!

W

ARNING

08

D

EMOVAL

 

AND

 

DISPOSAL

; T

ARGET

 G

ROUP

W

ARRANTY

 

AND

 

AFTER

-

SALES

 

SERVICE

; L

IABILITY

Summary of Contents for KSA TWIN 400 S12 24V

Page 1: ...KSA TWIN S12 24V DC CHAIN DRIVE according to Machinery Directive 2006 42 EC annex VI Assembly and Commissioning Instructions...

Page 2: ...INSTALLATION STEP 4 Changing the cable outlet position INSTALLATION STEP 5 Determine the casement brackets INSTALLATION STEP 6 Determine the frame brackets Application examples INSTALLATION STEP 7 De...

Page 3: ...e the health and safety requirements which apply to the machinery The ma chinery must then be designed and constructed taking into account the results of the risk assessment Separate documentation rel...

Page 4: ...ts must be hung or secured such way that in case one of the mounting elements fails it will not break away slam down or move in an uncontrolled manner by providing double suspensions safety scissors c...

Page 5: ...it is approved for one or several of these ambient conditions by the manufacturer Accident prevention regulations and guidelines is sued by the employers liability insurance association When working a...

Page 6: ...m v Speed s 400 8 0 mm s 8 0 mm s s 500 600 12 0 mm s 8 0 mm s s Stroke 400 600 mm 5 L Length see order data LM Distance in between chains see order data Components packed with drive u v 4x Countersu...

Page 7: ...ies PU pcs Part No M COM Comm module for synchronised multi drive systems 1 524177 DATA SHEET KSA TWIN S12 24V DC EXPLANATIONS ON THE PRODUCT LABEL 02 KSA TWIN 400 S12 Made in Germany Date 14W03 V2 0...

Page 8: ...and to ensure the supply of fresh air in the building The safety features of this product are crucial for compli ance with the Machinery Directive 2006 42 EC as well as standards EN 12101 2 The most i...

Page 9: ...al forces should act on the spindle chain or lever of the drives Additional warning signs might be required Predictable Misuse It is absolutely essential to avoid any foreseeable misuse of the drives...

Page 10: ...tly completed machine drive the following requirements must be met in order to allow cor rect assembly with other components to produce a com plete machine without compromising health and safety of pe...

Page 11: ...he chain moves with reduced speed in soft run mode from approx 40 mm before the CLOSED position If necessary repeat this step several times Manual unlocking of chain If soft run mode is not achieved o...

Page 12: ...e bracket during opening the position of the cable outlet must be changed Pull the cover cap of the drive profile by hand Pull the connection cable completely out of the cover cap Feed the cable caref...

Page 13: ...Casement bracket F33 Casement bracket F38 use on roof windows Heroal 085 180 with F16 use with K A1 K B1 K B2 K C1 K E1 K84 1 K87 use with K A1 K B1 K B87 Casement bracket F39 Casement bracket F73 us...

Page 14: ...uired on window frame 35 mm use with F14 und B1 mounting angle on the kerb upstand of dome rooflights INSTALLATION STEP 6 DETERMINE THE FRAME BRACKETS M6 28 32 45 33 16 17 34 60 9 5 93 5 5 5 13 13 3 5...

Page 15: ...ium window Detail of mounting on aluminium window Detail of mounting on wooden window Roof Frame mounting Friction hinged outward opening Frame mounting Bottom hung inward opening Casement mounting De...

Page 16: ...0 600 10 22 10 22 K A1 K B1 K B2 55 55 280 280 1 2 FAB 1 2 FAB F14 AK RA FL K C1 61 K E1 41 K84 1 39 5 1101 for stroke 400 1304 for stroke 500 600 55 55 1 2 FAB 1 2 FAB 10 22 22 10 F14 K C1 K E1 K84 1...

Page 17: ...ket K 87 with casement brackets F16 F33 Friction hinged casement D 550 5 for stroke 400 652 0 for stroke 500 600 286 1101 for stroke 400 1304 for stroke 500 600 43 43 1 2 FAB 1 2 FAB 20 14 11 min 28 5...

Page 18: ...ons please refer to the above mentioned hole layout drawings see chapter INSTALLATIONSTEP 5 7 or project specific documents and drawings INSTALLATION STEP 8 ASSEMBLY CASEMENT BRACKET L O C T I T E Car...

Page 19: ...L Kxxx RA Fxxx FL INSTALLATION STEP 9A ASSEMBLY FRAME BRACKET DRIVE MOUNTED ON THE WINDOW AT THE TOP Cable on casement Cable in glazing bead Connection cable routing on the casement The drive and its...

Page 20: ...damage shearing off kinking splitting Attach drive to the frame brackets Insert brass washers and firmly tighten with countersunk screws M8 Drive should freely swivel Check swiveling area see chapter...

Page 21: ...o 524310 1112 for stroke 400 1315 for stroke 500 600 1112 for stroke 400 1315 for stroke 500 600 1100 for stroke 400 1303 for stroke 500 600 1100 for stroke 400 1303 for stroke 500 600 10 22 22 A A A...

Page 22: ...4305 L 1 45 m 524310 L 2 90 m 524302 L kundenspezifisch Cover profile for surface mounted drives KSA TWIN with frame bracket sets K A1 K B1 K B2 K E2 K84 1 Profile length adjustable to the lenght of t...

Page 23: ...the cover profile in the area of the brackets If necessary paint the cover profile with the required colour Push on the cover profile so that it fits tightly If necessary remove the cover caps x from...

Page 24: ...ly insulated The running direction of the drive may be changed by in terchanging polarity reversal the wires BN brown BU blue Multi drive operation with master and slave Multi drive operation with M C...

Page 25: ...rely at the user s own risk and responsibility INSTRUCTIONS ON CONNECTION SAFETY CHECK AND PERFORMING TEST RUN INSTRUCTIONS ON CONNECTION Connecting drive cable Avoid any installation area with large...

Page 26: ...ems the legal requirement is once a year Check the system for operational avai lability on a regular basis This is also recommended for a system with purely natural ventilation At short intervals chec...

Page 27: ...oke exhaust system Do not operate the window during repair or adjustment work WARRANTY AND AFTER SALES SERVICE Basically our General Terms and Conditions of Goods and Services by the Elec trical Indus...

Page 28: ...28 Assembly Instruction KSA TWIN S12 24V DC CERTIFICATES 08...

Page 29: ...29 Assembly Instruction KSA TWIN S12 24V DC CERTIFICATES 08...

Page 30: ...30 Assembly Instruction KSA TWIN S12 24V DC CERTIFICATES 08...

Page 31: ...correct and up to date as possible we still cannot guarantee that they are free from mistakes and errors All information and data contained in this document are subject to alterations without prior no...

Page 32: ...n Tel 49 8271 8185 0 Fax 49 8271 8185 250 info aumueller gmbh de 9000017000_V0 1_KW05 14 www aumueller gmbh de AUM LLER AUMATIC GMBH Gemeindewald 11 86672 Thierhaupten Tel 49 8271 8185 0 Fax 49 8271 8...

Reviews: