IP68 with AUMA 3-phase AC motor
Terminal compartment additionally sealed against interior of actuator (double sealed)
Enclosure protection in accordance
with IEC 60529
According to AUMA definition, enclosure protection IP68 meets the following requirements:
●
Depth of water: maximum 8 m head of water
●
Continuous immersion in water: maximal 96 hours
●
Up to 10 operations during immersion
●
Modulating duty is not possible during immersion.
Pollution degree 4 (when closed), pollution degree 2 (internal)
Pollution degree according to
IEC 60664-1
2 g, 5 to 200 Hz
Resistant up to maximum 2g to vibration during start-up or for failures of the plant. Resistance against
frequent or continuously occurring vibration cannot be derived from this. Not valid in combination with
gearboxes. Detailed information on request.
Vibration resistance according to
IEC 60068-2-6
KS: Suitable for use in areas with high salinity, almost permanent condensation, and high
pollution.
Standard:
Corrosion protection
KX: Suitable for use in areas with extremely high salinity, permanent condensation, and
high pollution.
Options:
Double layer powder coating
Coating
AUMA silver-grey (similar to RAL 7037)
Standard:
Colour
Available colours on request
Options:
AUMA multi-turn actuators meet or exceed the lifetime requirements of EN 15714-2. Detailed information
can be provided on request.
Lifetime
< 72 dB (A)
Sound pressure level
Accessories
Wall mount controls including local controls separately mounted from actuator, connecting cables on
request.
Recommended when difficult to access or heavy operational vibration occurring on site.
Cable length between actuator and separately mounted local controls amounts to max. 100 m.
Wall mount controls
(wall mounted version)
AUMA CDT (Commissioning and Diagnostic Tool for Windows-based PC/notebook)
Software tool (via Bluetooth connec-
tion)
Further information
ATEX Directive 2014/34/EU
Machinery Directive 2006/42/EC
Low Voltage Directive 2014/35/EU
EMC Directive 2014/30/EU
RoHS Directive 2011/65/EU
EU Directives
Dimensions Multi-turn actuators TR-M30X – TR-M1000X/TR-MR30X – TR-MR1000X
Electrical data Multi-turn actuators TR-MR30X – TR-MR1000X
Reference documents
14.2.
Tightening torques for screws
Table 28:
Tightening torques for screws
Tightening torque [Nm]
Threads
Strength class
A2-80/A4-80
A2-70/A4-70
10
7.4
M6
24
18
M8
48
36
M10
82
61
M12
200
150
M16
392
294
M20
1,057
1,015
M30
2,121
1,769
M36
69