8.3.
Test run
8.3.1.
Direction of rotation at hollow shaft/stem: check
Figure 57: Direction of rotation of the hollow shaft/stem for operation in direction
CLOSE (“clockwise closing” version)
[1]
Threaded plug
[2]
Seal
[3]
Hollow shaft
[4]
Protective cap for stem protection tube
[5]
Stem
[6]
Stem protection tube
Valve damage due to incorrect direction of rotation!
→
If the direction of rotation is wrong, switch off immediately (turn selector switch
to OFF).
→
Eliminate cause, i.e. correct phase sequence for cable set wall bracket.
→
Repeat test run.
Check direction of rota-
tion
1.
Move actuator manually to intermediate position or to sufficient distance from
end position.
2.
Depending on the version: Unscrew threaded plug [1] with seal [2], protective
cap [4] or stem protection tube [6].
3.
Switch on actuator in direction CLOSE and observe direction of rotation at hollow
shaft [3] or stem [5]:
➥
The direction of rotation is correct if the actuator moves in direction CLOSE
and the hollow shaft in clockwise direction, or the stem moves downward.
4.
Correctly fit/screw on threaded plug [1] with seal [2], protective cap [4] for stem
protection tube [6], fasten thread.
8.3.2.
Limit switching: check
Procedure
1.
Set selector switch to LOCAL.
➥
The symbol
is indicated top left on the display.
46
TR-M30X – TR-M1000X
Commissioning
TR-MR30X – TR-MR1000X