15.5.3 Group
S
: Status indications
The status indications (group
S
) show the current operation mode
(see also page 51, clause 16.).
Status page
S0
(figure S1-0):
.
Line 1 shows the current operation mode (page 51, clause 16.).
.
Line 2 shows the current run commands which are transmitted to the
actuator via the local controls (push buttons) or via REMOTE.
.
Line 3 shows the actuator position in % of the travel (0 % = actuator is in
end position CLOSED, 100 % = Actuator is in end position OPEN). Is only
indicated if a position transmitter (potentiometer or RWG) is installed in
the actuator.
.
Line 4 shows the current status of the actuator, example: "
OPEN
POSITION
" = Actuator is in end position OPEN, "
RUNNING OPEN
" =
Actuator runs in position OPEN.
For further information regarding status
page S0 see page 25.
Status page
S1
(figure S1-1):
.
Faults are indicated here.
For further information
regarding status page S1 see
page 26.
Faults interrupt or prevent an operation
(see pages 25,26 and 59).
20
Part-turn actuators SG 03.3 – SG 04.3
with AUMATIC AC 01.1
Operation instructions
OFF
S0
RUNNING OPEN
S1
S2
FAULT IND.
NO FAULT
WARNING IND.
NO WARNING
E2
100%
S3
NOT READY IND.
READY
Figure S1: Overview status indications
OFF
S0
RUNNING OPEN
E2
100%
Line 3: Actuator position
Line 1: Operation mode
Line 4: Actuator status
Line 2: Run commands
Figure S1-0
S1
FAULT IND.