![AUMA SARVEx 07.2 Operation Instructions Manual Download Page 75](http://html1.mh-extra.com/html/auma/sarvex-07-2/sarvex-07-2_operation-instructions-manual_3016487075.webp)
Table 32:
Signal on temperature monitoring of PTC tripping device active
Remedy
Possible causes
Check external power supply of heating sys-
tem.
Heating system (wiring diagram designation:
R5 H
) failure
for ambient temperatures below –30 °C
Switch off heater control unit
M1338
Switch off external power supply of heating
system.
Contact AUMA service
Heating system defective
PTC tripping device defective
for ambient temperatures exceeding –30 °C
11.2.1.
Signal for temperature warning of PTC tripping device
The “Motor protection tripped” signal (wiring diagram designation:
TMS-M
) must be
monitored:
“Motor protection tripped” = contact NC open (contact NO = closed)
When operating in combination with a suitable heating system within an ambient
temperature range exceeding the indicated temperature range of the sub-assembly,
the signal has to be integrated into the system circuit. The integrated heating system
within actuator controls (wiring diagram designation:
R5 H
) must be checked in the
event of the “Motor protection tripped” signal (wiring diagram designation
TMS-M
).
Switch off the power supply of the heating system for temperatures significantly
exceeding –30 °C! Excessive device temperature signal due to failure of the heating
system might be the cause.
It is imperative to ensure the presence of the power supply of the optional heating
system for temperatures below –30 °C!
11.3.
Fuses
11.3.1.
Fuses within the actuator controls
F5
Automatic reset fuse as short-circuit protection for external 24 V DC supply for
customer (refer to wiring diagram)
11.3.2.
Motor protection (thermal monitoring)
In order to protect against overheating and impermissibly high surface temperatures
at the actuator, PTC thermistors are embedded in the motor winding. Motor protection
trips as soon as the max. permissible winding temperature has been reached.
The actuator is switched off and the following signals are given:
●
LED 3 (motor protection trippped) on the local controls is illuminated.
●
The status indications
S0007
or
S0011 Failure
display a fault.
The fault
Details
is displayed when selecting
Thermal fault
.
The motor has to cool down before operation can be resumed.
Depending on the parameter setting (motor protection behaviour), the fault signal is
either automatically reset or the the fault signal has to be reset using RESET push
button with selector switch position Local operation (LOCAL).
Proof-test motor protection
The functionality of the motor protection must be verified at the latest when performing
the maintenance (refer to chapter <Servicing and maintenance>).
The test is performed by simulating the motor protection signal via actuator controls
local controls:
Required user level:
Specialist (4)
or higher.
Diagnostics M0022
TMS proof test M1950
Test procedure:
1.
Set selector switch to position 0 (OFF).
75
SAVEx 07.2 – SAVEx16.2/SARVEx 07.2 – SARVEx16.2 Control unit: electronic (MWG)
ACVExC 01.2 Non-Intrusive
Corrective action