10.3.
Limit switching: set
Valve damage at valve/gearbox due to incorrect setting!
→
When setting with motor operation: Stop actuator prior to reaching end of travel
(press STOP push button).
→
For limit seating, provide for sufficient backlash between end position and
mechanical end stop due to potential overrun.
Customer settings M0041
Limit switching M0010
Set end pos.CLOSED? M0084
Set end pos. OPEN? M0085
Select main menu
1.
Set selector switch to position 0 (OFF).
2.
Press push button C and hold it down for approx. 3 seconds.
➥
Display goes to main menu and indicates:
▶ Display
Select parameter
3.
Select parameter either:
→
click via the menu
to parameter, or
→
via direct display: press and enter ID
M0084
.
➥
Display indicates:
Set end pos.CLOSED?
CLOSED or OPEN
4.
Select via
Up ▲ Down ▼
:
→
▶ Set end pos.CLOSED? M0084
→
▶ Set end pos. OPEN? M0085
➥
The black triangle
▶
indicates the current selection.
5.
Press
Ok
.
➥
The display indicates either:
-
Set end pos.CLOSED? CMD0009 →
continue with step 9
-
Set end pos. OPEN? CMD0010 →
continue with step 12
-
Specialist (4) →
continue with step 6
User login
6.
Use
Up ▲ Down ▼
to select user:
Information: Required user level:
Specialist (4)
or higher
➥
The symbols have the following meaning:
-
black triangle:
▶
= current setting
-
white triangle:
▷
= selection (not saved yet)
7.
Press
Ok
to confirm selected user.
➥
Display indicates:
Password 0***
8.
Enter password (
→
enter password).
➥
The display indicates either:
-
Set end pos.CLOSED? CMD0009 →
continue with step 9
-
Set end pos. OPEN? CMD0010 →
continue with step 12
60
SAV 07.2 – SAV 16.2 / SARV 07.2 – SARV 16.2 Control unit: electronic (MWG)
Commissioning (basic settings)
ACV 01.2 HART