Safety standards
Safety measures and safety equipment must comply with the respectively valid
national on site specifications. All externally connected devices shall comply with
the relevant safety standards applicable for the place of installation.
Connecting cables,
cable glands, reducers,
blanking plugs
●
We recommend using connecting cables and connecting terminals according
to rated current (I
N
) (refer to motor or electrical data sheet).
●
For device insulation, appropriate (voltage-proof) cables must be used. Specify
cables for the highest occurring rated voltage.
●
To avoid contact corrosion, we recommend the use of sealing agents for cable
glands and blanking plugs made of metal.
●
Use connecting cable with appropriate minimum rated temperature.
●
For connecting cables exposed to UV radiation (outdoor installation), use UV
resistant cables.
●
For the connection of position transmitters, screened cables must be used.
Cable installation in ac-
cordance with EMC
Signal and fieldbus cables are susceptible to interference. Motor cables are
interference sources.
●
Lay cables being susceptible to interference or sources of interference at the
highest possible distance from each other.
●
The interference immunity of signal and fieldbus cables increases if the cables
are laid close to the earth potential.
●
If possible, avoid laying long cables and make sure that they are installed in
areas being subject to low interference.
●
Avoid parallel paths with little cable distance of cables being either susceptible
to interference or interference sources.
6.2.
Open terminal compartment
Figure 11: Open terminal compartment (example of I/O interface)
[1]
Cover
[2]
Screws
[3]
Cable entry
[4]
Blanking plug
[5]
Cable gland (not included in scope of delivery)
17
PF-Q80 – PF-Q600
Electrical connection